Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
104
3.2.6.2
Parameter window
K: Blinds (6 A)
In this parameter window all settings for the
Output
K
:
Output (6 A
) are
undertaken.
This parameter is visible if in parameter window
,
Blinds
has been selected with parameter
Output K
(Shutter) (6 A)
.
Reaction on bus voltage failure
Options: unchanged
UP
DOWN
STOP
The output can adopt a defined state on bus voltage failure using this
parameter.
•
unchanged:
The relay position of the outputs remains unchanged.
A movement process is thus performed to completion.
•
UP/DOWN/STOP:
A fixed relay contact position is set.
Note
If the relay has been switched immediately before a bus voltage failure,
it may not be possible to implement the options
UP
and
DOWN
.
The energy stored in the Room Master is not sufficient for this purpose.