ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
105
Reaction on bus voltage recovery
Options: unchanged
UP
DOWN
STOP
This parameter defines how the output should respond with bus voltage
recovery.
•
unchanged:
The current state is retained.
•
UP/DOWN/STOP:
A fixed relay contact position is set.
Position after reference movement
Options: deactivated
no
reaction
move to saved position
This parameter enables the
Reference movement
communication object and
defines how the Room Master responds after a reference movement.
•
deactivated:
The communication object
Reference movement
is not
visible. No referencing can be performed.
•
no reaction:
The blinds remains either up or down in the reference
position after the reference movement.
•
move to saved position:
The blind is retracted to the position in which it
was before the reference movement was performed.
If the automatic function was activated for the blinds before the
reference movement, then the function is re-activated again
automatically after the stored position is reached.
Note
If during a reference movement a direct or automatic movement of
position command is received, then the reference movement is performed
first and the received target position is approached afterwards.
For further information see:
Determination of the current position
, page 227
Move to position [0…255]
Options: directly
indirectly via up
indirectly via down
indirectly via shortest way
•
directly:
The blind moves with a position command from the current
position directly to the new target position.
•
indirectly via up/indirectly via down:
The blind will initially move fully up
or down after a movement command is received and then move to the
target position.
•
indirectly via shortest way:
The blind will initially move fully up or down
after a movement command is received depend on which path is the
shortest. Thereafter the blind moves to the target position.