ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
132
Caution
The RM/S is supplied ex-works with a default setting (factory default).
This ensures the fan setting is switched off when the bus voltage is
applied to the relay for the first time.
Thus, damage to the device due to unintentional switch on during
transport, e.g. due to vibration, is avoided.
It is advisable to apply a bus voltage before connecting the fan in order to
achieve a defined switch state of the fan. This eliminates the possibility of
the destruction of the fan due to an incorrect contact setting.
Enable communication object
"Forced operation" 1 bit
Options: no
yes
•
yes:
A 1 bit
Forced operation
communication object is enabled.
Further parameters appear at the same time:
Forced operation on object value
Options: 1
0
•
1:
Forced operation is activated by a telegram with value 1.
•
0:
Forced operation is activated by a telegram with value 0.
Behaviour with forced operation
Options: unchanged
OFF
ON
This parameter defines how the fan should respond with forced
operation.