ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
133
Enable automatic operation
Options: no
yes
•
yes:
Automatic mode is enabled; an additional -
Automatic operation
parameter window appears.
Function time on ON
Options: none
switching
delay
minimum
time
The function
Time
at fan ON is defined with this.
•
none:
The time function is executed.
•
switching delay:
The fan is switched on using this delay.
•
minimum time:
The fan remains ON for at least this time.
With option
switching delay
the following parameters appear:
Time in s [1…65,535 x 0.1]
Options: 1…20…65,535
The fan is switched on using this delay.
With option
minimum time
the following parameters appear:
Time in s [1…65,535]
Options:
1…20…65,535
The fan remains ON for at least this time.
Function time on OFF
Options: none
switching
delay
minimum
time
The function
Time
at fan OFF is defined with this.
•
none:
The time function is executed.
•
switching delay:
The fan is switched off using this delay.
•
minimum time:
The fan remains OFF for at least this time.
With option
switching delay
the following parameters appear:
Time in s [1…65,535 x 0.1]
Options:
1…20…65,535
The fan is switched off using this delay.
With option
minimum time
the following parameters appear:
Time in s [1…65,535]
Options: 1…20…65,535
The fan remains OFF for at least this time.