3.3.3
Control input
3.3.3.1
Communication objects
HVAC System
1 Control value/2 pipe
No.
Function
Object name
Data type
Flags
29 Control
value
HEATING/COOLING
Control input
EIS 6, 1 byte
DPT 5.001
C, W
This communication object is enabled if in parameter window
Control input
the parameter
HVAC System
has been selected with the option
1 Control value/2 pipe
.
Using this communication object the control value HEATING or COOLING is predefined as
a 1 byte % value.
Telegram value:
0 % = OFF, no heating or cooling
100 % = ON, largest control value, maximum heating or cooling
30 Control
value
COOLING (extra!)
Control input
EIS 6, 1 byte
DPT 5.001
C, W
Note
Independent of communication object 29, the COOLING valve can be
additionally controlled without monitoring via the communication object 30.
This communication object is enabled if in parameter window
Control input
the parameter
HVAC System
has been selected with the option
1 Control value/2 pipe
.
Using this communication object the control value COOLING is predefined as a 1 byte %
value.
Telegram value:
0 % = OFF, no cooling
100 % = ON, largest control value, maximum cooling
31
Not assigned.