ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
182
3.3.4
Communication objects
Valve HEATING
No.
Function
Object name
Data type
Flags
33
Block
Valve HEATING
EIS 1, 1 bit
DPT 1.003
C, W
This communication object is enabled if in parameter window -
Function
the parameter
Enable
communication object “Disable" 1 bit
has been selected with option
yes
.
The valve is disabled with this communication object.
If the block is enabled, the highest priority is retained and the current control value is retained,
i.e., the valve remains stationary. Movement to a target position which may not have yet been
achieved will be performed to completion. If the block is removed, the target position which
has been set without the block is approached.
Telegram value:
0 = valve not blocked
1 = valve blocked
34
Forced operation
Valve HEATING
EIS 1, 1 bit
DPT 1.003
C, W
This communication object is enabled if in parameter window -
Function
the parameter
Enable
communication object "Forced operation" 1 bit
is selected with option
yes
.
This communication object sets the output in a defined state and blocks it. If the value 1 is
received, forced operation is activated and the output triggers the programmed valve position.
If the value 0 is received forced operation ends. The contact position is retained until the RM/S
receives a new setting signal.
Telegram value:
0 = end forced operation
1 = start forced operation