ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
193
3.3.6.4
Communication objects
Value/forced operation
No.
Function
Object name
Data type
Flags
45
Block
Input a:
Value/forced
operation
EIS 1, 1 bit
DPT 1.003
C, W
This communication object is enabled if in parameter window
a: Value/forced operation
the parameter
Enable communication object "Disable" 1 bit
has been selected with option
yes
.
Using the communication object
Block
the input can be blocked or enabled. With activated
communication object
Block
the inputs are blocked.
Note
When the input is blocked there is fundamentally no reaction to a signal
change, but:
– Waiting for a long button operation or a minimum signal duration
is suspended.
– The parameter setting
8 bit scene
is ended with saving.
– Communication objects continue to be updated and sent if necessary.
When enabling an input, a change of the signal states (as opposed to before
the block) leads to immediate processing, e.g.:
– The minimum actuation or detection of a long/short button push starts.
– Communication objects send their current value if necessary.
Telegram value:
0 = enable input a
1 = block input a