ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
198
No.
Function
Object name
Data type
Flags
138
Scene
Output A
1 byte Non EIS
DPT 18.001
C, W
This communication object is enabled if in parameter window
A: Output (20 A/16 AX C-Load)
the parameter
Enable function scene
has been selected with the option
yes
.
Using this 8 bit communication object a scene command can be sent using a coded telegram.
The telegram contains the number of the respective scene as well as the information if the
scene is to be recalled, or if the current switch state is to be assigned to the scene.
Telegram format (1 byte):
MXSSSSSS
(MSB) (LSB)
M: 0 – scene is recalled
1 – scene is stored (if allowed)
X: not used
S: Number of the scene (1-64: 00000000 … 00111111)
KNX 1 byte telegram value
Decimal
Hexadecimal
Meaning
00 or 64
01 or 65
02 or 66
…
63 or 127
00h or 40h
01h or 41h
02h or 42h
…
3Fh or 7Fh
Call scene 1
Call scene 2
Call scene 3
…
Call scene 64
128 or 192
129 or 193
130 or 194
…
191 or 255
80h or B0h
81h or B1h
82h or B2h
…
AFh or FFh
Store scene 1
Store scene 2
Store scene 3
…
Store scene 64
For further information see:
, page 269.
139
Forced operation
Output A
1 bit (EIS 1)
DPT 1.003
C, W
This communication object is enabled if in parameter window
A: Output (20 A/16 AX C-Load)
the parameter
Enable function forced operation
has been selected with the option
yes
and the
parameter
Type of object “Forced operation”
has been selected with 1 bit.
If the object receives the value 1, the output is forcibly set to the parameterised switch position
which has been set in the parameter window
Output A (20 A/16 AX C-Load)
. The forced
positioning of the contact should remain until forced operation is ended. This is then the case
when a 0 is received via the communication object
Forced operation
.
Please note that the function
Forced operation
and a bus failure have a higher priority on the
, page 215.