ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
202
No.
Function
Object name
Data type
Flags
242
Move louvre [0…255]
Output K
1 byte (EIS6)
DPT 5.001
C,W,T
This communication object is enabled if in parameter window
Enable Outputs K-U
the parameter
Output K (Shutter) (6 A)
has been selected with
Shutter
or
Blinds
.
This communication object serves the movement and the feedback of a defined louvre
position and is therefore only available in shutter mode.
If a telegram is received on this communications object, the louvres are then positioned in
accordance with the received value. If the shutter is currently moving, the movement will
continue to the target position and positioning of the louvres is then undertaken.
Telegram value:
0
= Lamella fully UP
… = intermediate position
255 = Lamella DOWN
243
Reference movement
Output K
1 bit (EIS1)
DPT 1.008
C, W
This communication object is enabled if in parameter window
Enable Outputs K-U
the parameter
Output K (Shutter) (6 A)
has been selected with
Shutter
or
Blinds
.
This communication object is used for the compensation of deviations in the position,
e.g. after frequent UP/DOWN in the intermediate positions. The shutter or blinds are moved to
the end position (0 = top, 1 = bottom) and back.
If a telegram is received on this communication object, the shutter is moved fully upwards or
downwards.
The current position is stored in order to move the shutter later to the parameterised position
after the reference movement. If the option
move to saved position
is set, and if the automatic
function was set for the shutter before the reference movement, then the function
Automatic
will be reactivated after the saved position is reached.
Telegram value:
0 = reference movement fully upwards
1 = reference movement fully downwards