ABB i-bus
®
KNX
Planning and application
© 2008 ABB STOTZ-KONTAKT GmbH
213
4.1.4
Operation of shutters
1 button operation
Push button 1 and push button 2 operate shutter 1 from different locations.
With a short button operation the shutter moves (in the opposite direction to
the last movement); a long operation offsets the louvre.
Logical connection of the group addresses:
Push button 1
Shutter 1
Binary input
(telegram)
Shutter output
(telegram)
Shutter UP/DOWN
1/1/1 1/1/1
Move shutter UP/DOWN
STOP/lamella adjustment
1/1/2 1/1/2
Lamella adj./STOP UP/DOWN
Upper limit position
1/1/3 1/1/3
Status of upper position
Lower limit position
1/1/4 1/1/4
Status of lower position
Push button 2
Binary input
(telegram)
Shutter UP/DOWN
1/1/1
STOP/lamella adjustment
1/1/2
Upper limit position
1/1/3
Lower limit position
1/1/4
*
Feedback is signalled to the binary input via the communication objects
Upper limit position
and
Lower limit position
to indicate if the shutter actuator is in the end position. If this is not
possible 2 button operation is recommended.
In parameter window
a: Shutter sensor
the settings for button 1 and button 2
appear as follows: