ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
43
Scan input after download,
bus reset and bus voltage recovery
Options:
Fault
monitoring
option:
yes/no
yes
Inactive wait state after bus voltage-
recovery in s [0…30,000]
Options:
Fault
monitoring
option:
0…30,000
0
Communication object “Switch 1”
Fixed preset to
yes
.
Reaction on closing the contact
and/or with short operation
Options:
Fault
monitoring
option:
ON
partly
adjustable
OFF
TOGGLE
no reaction
terminate cyclic sending
Reaction on opening the contact
and/or with long operation
Options:
Fault
monitoring
option:
ON
partly
adjustable
OFF
TOGGLE
no reaction
terminate cyclic sending
Cyclic sending
Options:
Fault
monitoring
option:
yes/no
yes
On object value
Options:
Fault
monitoring
option:
0
0
or
1
1
0 or 1
Telegram repeated every …
in s [1…65,535]
Options:
Fault
monitoring
option:
1...60...65,535
30
Note
Fault messages are generally passed onto the main bus. With 500 fault
messages, the option 30 s means that every 60 ms a telegram is sent on
the main bus. For this reason it is essential to ensure that the send delay
time is set, so that no telegram is lost if the bus voltage fails.