ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
49
3.2.2.3
Parameter window
a: Shutter Sensor
The operating mode allows the operation of shutters and blinds with buttons
or switches.
This parameter window is visible if in parameter window
page 32, the option
Shutter Sensor
in the parameter
Input a (binary input,
contact scanning)
has been selected.
Enable communication object
"Disable" 1 bit
Options: no
yes
•
yes:
The 1 bit
Block
communication object is enabled.
This can be used to block the input.
Note
If the input is disabled and the option
Cyclic sending
is set, the last state is
still sent regardless of the block. The option block still blocks the physical
input, sending continues internally.
Debounce time
Options: 10/20/30/50/70/100/150 ms
Debouncing prevents unwanted multiple operations of the input, e.g. due to
bouncing of the contact.