3.2.2.4.1 Parameter
Distinction between
short and long
operation – no
If the option
no
is selected with the parameter difference between long and
short operation, the following parameters appear in the parameter window
page
Activate minimum signal time
Options: no
yes
•
yes:
The following parameters appear:
for rising edge
in value x 0.1 s [1…65,535]
Options: 1…10…65,535
Note
A rising edge corresponds to a normally open contact function.
for falling edge
in value x 0.1 s [1…65,535]
Options: 1…10…65,535
Note
A falling edge corresponds to a normally closed contact function.