3.2.6.1.1 Parameter window
K: Shutter (6 A)
- Drive
In this parameter window all settings for the shutter drive are undertaken.
This parameter is visible if in parameter window
page 89, the option
Shutter
has been selected with parameter
Output K
(Shutter) (6 A)
.
Total travel time
in s [1…18,000]
Options: 1…60…18,000
This parameter defines the total travel time from the upper end position to
the lower end position.
Duration of louvre adjustment
in ms [30…65,535]
Options: 30…300…65,535
This parameter determines the switch on duration with the louvre
adjustment, i.e. the time for which a louvre is rotated after it receives
a
STOP/lamella adjustment
command.
Total travel time of louvres
[0…100 %] in ms [30…65,535]
This parameter defines the total movement time during louvre adjustment,
i.e. the time required to rotate the louvres from one end position to the other
end position.
Note
On larger louvres there is a mechanical dead zone time involved until the
shutter reacts. For this reason the total movement time will be extended
by this reaction time.