ABB i-bus
®
KNX
Planning and application
© 2008 ABB STOTZ-KONTAKT GmbH
217
4.2.2.1
Staircase lighting
After the staircase lighting time T
ON
the output switches off automatically.
For every telegram with the value 1 the time restarts (“retrigger function”),
if the parameter
Extending staircase lighting by multiple operation
("pumping up")
, page 69, is set to
no, no pump up possible
.
The response is the fundamental response of the staircase lighting function
Via “pumping up” – actuation of the push button several time in succession –
the user can adapt the staircase lighting to current needs. The maximum
duration of the staircase lighting time can be set in the parameters.
If the device receives a further ON command when the staircase lighting
is switched on, the staircase lighting time is added to the remaining period.