Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
53
3.2.2.4
Parameter window
a: Value/Forced
operation
This operating mode allows the sending of values of any data types.
This parameter window is visible if in the parameter window
Value/Forced operation has been
selected in the p
arameter
Input a
(
binary input, contact scanning
).
Enable communication object
"Disable" 1 bit
Options: no
yes
•
yes:
The 1 bit
Block
communication object is enabled.
This can be used to block the input.
Note
If the input is disabled and the option
Cyclic sending
is set, the last state is
still sent regardless of the block. The option block still blocks the physical
input, sending continues internally.
Debounce time
Options: 10/20/30/50/70/100/150 ms
Debouncing prevents unwanted multiple operations of the input, e.g. due to
bouncing of the contact.