Technical data of SAK17 (GHV9240001V0013)
Supply
Rated voltage
12 V DC
Battery capacity
17 Ah
Temperature range
Operation
−
20 … +50 °C
Transport
−
20 … +50 °C
Storage
−
20 … +20 °C
Dimensions
167 × 181 × 76 mm (H x W x D)
Weight
6.8 kg
Service life
5 years
Tab. 13: Technical data of SAK17
13.2.7
Technical data of AM/S 12.1 (GHQ6310062R0111)
Supply
Power Supply
May be connected only to the Uninterruptible
EIB / KNX Power Supply SU/S 30.640.X
Rated voltage
12 V DC
Battery capacity
1 Ah
Charging current
150 mA
Charging time
Max. 10 h
Mains power failure backup time
10 minutes (depending on the bus load; the
mains power failure backup time decreases as
the battery module ages)
Safety
Temperature sensor
Integrated
Fuse
Self-healing (integrated)
Connections
Power Supply
2 screw terminals
Temperature sensor
2 screw terminals
Connection cross section
Fine stranded: 0.2 – 2.5 mm
2
Solid: 0.2 – 4 mm²
Degree of protection
IP 20, EN 60 529
Temperature range
Operation
+5 … +45 °C
Transport
−
25 … +50 °C
Storage
−
25 … +20 °C
Design
Modular installation device (MDRC)
Modular installation device
Design
pro M
Housing/color
Plastic, gray
Dimensions
Dimensions
90 × 144 × 64.5 mm (H x W x D)
Mounting width in space units
8 modules, 18 mm each
Mounting depth
68 mm
Mounting
35 mm mounting rail
According to EN 60715
Mounting position
Horizontal
Weight
0.72 kg
Declaration of conformity
CE according to EMC Directive and Low-Voltage
Directive
Tab. 14: Technical data of AM/S 12.1
Summary of Contents for i-bus KNX SU/S 30.640.2
Page 1: ... PRODUCT MANUAL ABB i bus KNX SU S 30 640 2 Uninterruptible KNX Power Supply 640 mA ...
Page 2: ......
Page 8: ......
Page 18: ......
Page 24: ......
Page 26: ......
Page 28: ......
Page 30: ......
Page 32: ......
Page 34: ......
Page 36: ......
Page 42: ...ABB i bus KNX Appendix 42 9AKK107992A4580_EN Rev A SU S 30 640 2 13 3 Notes ...
Page 43: ...ABB i bus KNX Appendix SU S 30 640 2 9AKK107992A4580_EN Rev A 43 ...