ABB i-bus
®
KNX
Commissioning
SUG/U 1.1 | 2CDC508171D0201 13
3
Commissioning
3.1
Overview
The
Split Unit Gateway/…
application is available for the SUG/U 1.1 Split Unit Gateway.
Programming requires ETS.
In addition to the ETS application you will require the "ABB SUG/U 1.1" app for commissioning; this can be
obtained free from the KNX Online Shop.
For use of the i-bus
®
Tool, see: Integration in the i-bus® Tool, p. 6.
The Split Unit Gateway forms the interface between the KNX system and climate control equipment from a
wide range of manufacturers, also referred to as split units. The device converts KNX telegrams to infrared
commands and sends them to the split unit. The split unit can therefore be operated via KNX using any
operating element.
The following functions can be sent direct to the split unit:
•
On/Off
•
Switches the split unit on or off. You can also parametrize a switching off delay.
•
Specify setpoint temperature including parametrizable setpoint temperature limits
•
The setpoint is sent to the split unit. It is then regulated by the split unit itself.
•
The setpoint temperature can be sent direct (2 byte value) and/or regulated up/down by 1 bit.
•
Set operating mode (Automatic, Heating, Cooling, Ventilation, Drying)
•
These are the standard operating modes for most split units.
•
Fan speed control
•
Fan speeds can be controlled by a 1-byte value (with different codes) or regulated up/down by
1 bit.
•
Horizontal and vertical swing
•
Slat movement can be activated/deactivated on many split units.
•
Activate Silent Mode
•
Lots of new split units support this function. Activating this function reduces the output of the
split unit's external unit. This reduces noise, e.g. at night.
Summary of Contents for i-bus KNX SUG/U 1.1
Page 1: ...ABB i bus KNX SUG U 1 1 Split Unit Gateway Product Manual ...
Page 2: ......
Page 4: ......
Page 52: ...ABB i bus KNX Appendix 50 2CDC508171D0201 SUG U 1 1 A 4 Notes ...
Page 53: ...ABB i bus KNX Appendix SUG U 1 1 2CDC508171D0201 51 Notes ...
Page 54: ...ABB i bus KNX Appendix 52 2CDC508171D0201 SUG U 1 1 Notes ...
Page 55: ......