ABB i-bus® KNX
PARAMETERS
7.4.116
Control value
This parameter is used to define the control value after bus voltage recovery or ETS download. The set
control value is valid until a new control value is calculated by the controller in the controller mode or a
new control value is received via the bus (
ABB i-bus® KNX
) in the actuator mode.
Option
0 … 100 %
Prerequisites for visibility
– Parameter
Control value after bus voltage recovery
Option
Selection
or
– Parameter
Control value after ETS download
Option
Selection
• The parameter is in the parameter window
7.4.117
Control value on input fault
This parameter is used to define the control value set if there is an error on the monitored temperature
input. The control value applies only to the active operating mode. The control value is valid until the er-
ror is corrected.
Option
0 … 25 … 100 %
Prerequisites for visibility
\ Option
Controller channel
– Parameter
Option
Activated
– Parameter
\
Option
On physical device input x
• The parameter is in the parameter window
7.4.118
Control value after exceeding monitoring time
This parameter is used to define the control value set if the monitoring time is exceeded. The control
value applies only to the active operating mode.
Option
0 … 25 … 100 %
Prerequisites for visibility
\ Option
Controller channel
– Parameter
Option
Activated
– Parameter
\
Option
On group object
• The parameter is in the parameter window
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
122