ABB i-bus® KNX
PARAMETERS
7.4.45
Window open if [controller]
This parameter is used to define the value of the group object
terpreted as the status "Window open".
When the status "Window open" is received, the controller switches to the operating mode
Building
Protection (Building Protection heating = frost protection, Building Protection cooling = heat protec-
tion).
Option
Value 0
Value 1
Prerequisites for visibility
– Parameter
\
Option
Controller channel
– Parameter
Option
Via group object
• The parameter is in the parameter window
.
7.4.46
Filter
This parameter is used to set a floating mean value filter.
More information: →
Floating mean value, Page 178
.
Option
Deactivated
The floating mean value filter is deactivated.
Low (floating mean value over
30 seconds)
The mean value filter is active. The mean value is determined over a time of 30 seconds.
Medium (floating mean value
over 60 seconds)
The mean value filter is active. The mean value is determined over a time of 60 seconds.
High (floating mean value over
120 seconds)
The mean value filter is active. The mean value is determined over a time of 120 seconds.
Prerequisites for visibility
\ Option
Temperature
sensor
• The parameter is in the parameter window
.
7.4.47
Fill level reached if [input x]
This parameter is used to define the sensor contact position that is interpreted as the status "Fill level
alarm".
Option
Contact open
Contact closed
Prerequisites for visibility
\ Option
Fill level sensor
• The parameter is in the parameter window
.
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
82