ABB i-bus® KNX
PARAMETERS
7.4.48
Fill level reached if [controller]
This parameter is used to define the value of the group object
status "Fill level alarm".
Note
When the controller receives the status "Fill level alarm", cooling is interrupted and the operating mode
Building Protection
is activated. Building Protection remains active until the controller receives the sta-
tus "No fill level alarm".
The fill level alarm acts only on the
Cooling
operating mode, and the operating mode can therefore be
switched to
Heating
(if available) at any time.
Option
Value 0
Value 1
Prerequisites for visibility
– Parameter
\
Option
Controller channel
– Parameter
Basic-stage cooling [controller]
all options except
Deactivated
– Parameter
Option
Via group object
• The parameter is in the parameter window
.
7.4.49
Weighting of external measurement 1
This parameter is used to define the weighting with which the external measurement is included in the
calculation of the actual temperature.
More information: →
Weighting of the temperature inputs, Page 177
.
Option
0 … 100 %
Prerequisites for visibility
– Parameter
\
Option
Controller channel
– Parameter
\
Options
Via group object / Via phys. device input or group
object
• The parameter is in the parameter window
.
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
83