ABB i-bus® KNX
PARAMETERS
7.4.98
Standby heating setpoint
This parameter is used to define the setpoint temperature for the
Standby heating operating mode.
More information: →
Explanation of the operating modes, Page 174
Note
The temperature value specified here must be lower than the value in the parameters
Comfort heating and cooling setpoint
. A difference of at least 2 K is recommended.
Note
The controller ensures that the setpoint temperature is not exceeded when the actual temperature in-
creases. The operating mode is not changed.
Option
10 … 19 … 40 °C
Prerequisites for visibility
– Parameter
\
Option
Controller channel
– Parameter
Basic-stage heating [controller]
all options except
Deactivated
– Parameter
Options
Comfort, Standby, Economy, Building Protection / Comfort,
Standby, Building Protection
– Parameter
Setpoint specification and adjustment
Option
Absolute
• The parameter is in the parameter window
7.4.99
Comfort heating and cooling setpoint
This parameter is used to define the setpoint temperature for the
Comfort heating and Comfort cooling
operating modes.
More information: →
Explanation of the operating modes, Page 174
Note
The temperature value specified here must be between the values in the parameters
and
. A difference of at least 2 K is recommended.
Option
10 … 21 … 40 °C
Prerequisites for visibility
– Parameter
\
Option
Controller channel
– Parameter
Basic-stage heating [controller]
all options except
Deactivated
– Parameter
Basic-stage cooling [controller]
all options except
Deactivated
\ Parameter
setpoint = Comfort cooling setpoint
\ Option
Yes
• The parameter is in the parameter window
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
113