ABB i-bus® KNX
PARAMETERS
7.4.104
Comfort heating setpoint = Comfort cooling setpoint
This parameter is used to define whether a common setpoint temperature is used for
Comfort heating
and
Comfort cooling.
More information: →
Explanation of the operating modes, Page 174
Option
No
Two different setpoint temperatures (setpoints) can be set for
Comfort heating
and
Comfort
cooling
.
The following dependent parameters are shown:
•
•
Yes
A common setpoint temperature is used for
Comfort heating
and
Comfort cooling
.
The following dependent parameters are shown:
•
Hysteresis for Heating/cooling changeover
•
Comfort heating and cooling setpoint
Prerequisites for visibility
– Parameter
\
Option
Controller channel
– Parameter
Basic-stage heating [controller]
all options except
Deactivated
– Parameter
Basic-stage cooling [controller]
all options except
Deactivated
• The parameter is in the parameter window
7.4.105
Setpoint indication on slave display
This parameter is used to define how the setpoint is indicated on the display for a slave.
Option
Absolute
The setpoint is indicated as an absolute value.
Relative
The setpoint is indicated as a relative value.
Prerequisites for visibility
\ Option
Controller channel
\ Parameter
room control unit to physical device input a
\ Option
No
• The parameter is in the parameter window