ABB i-bus® KNX
PARAMETERS
7.4.159
Send cyclically every
This parameter is used to define the cycle in which the value of the group object is sent.
Note
The possible options and default values depend on the higher-level parameter.
Option
00:00:30 … 00:05:00 … 18:12:15 hh:mm:ss
00:00:30 … 00:01:00 … 18:12:15 hh:mm:ss
Prerequisites for visibility
• The parameter appears at various points in the application. The visibility is dependent on the applica-
tion and the higher-level parameter.
7.4.160
Cyclical monitoring
The cyclical monitoring is activated/deactivated with this parameter.
More information: →
Cyclical monitoring, Page 193
Option
Deactivated
The cyclical monitoring is deactivated.
Activated
The following dependent parameters are shown:
•
•
Monitor receipt of group object "Operating mode normal (master)"
•
Monitor receipt of group object "Heating/cooling changeover"
•
Monitor receipt of group object "Window contact"
•
Monitor receipt of group object "Dew point alarm"
•
Monitor receipt of group object "Fill level alarm"
•
Monitor receipt of "Control value heating/cooling" group objects
Prerequisites for visibility
• The parameter is in the parameter window
7.4.161
Time interval for cyclical monitoring
This parameter is used to define the time interval during which a value must be received on the moni-
tored group object.
More information: →
Cyclical monitoring, Page 193
Note
The monitoring cycle in the device should be at least quadruple the cyclical sending time of the send-
ing device. As a result, the reactions set will not be triggered immediately if a signal is missing, e.g.
due to high bus load.
Option
00:00:30 … 01:00:00 … 18:12:15 hh:mm:ss
Prerequisites for visibility
• The parameter appears at various points in the application. The visibility is dependent on the applica-
tion and the higher-level parameter.