ABB i-bus® KNX
GROUP OBJECTS
8.7
Group objects Channel X – Actuator
Function
Group object name
Data point
type
Length
Flags
Control value Heating
Channel X – Actuator
DPT 5.001
1 byte
C
W T U
This group object is used to receive the control value Heating via the bus (ABB i-bus® KNX). This control value is output via the selected output in operating mode
Heating
.
Telegram value:
•
0 … 100 %
Note
If DPT 5.001 (percentage) is used for the activation, the value displayed for the group object may vary from the actual value due to rounding differences. The actual
value of the group object can be seen by viewing the hexadecimal value (this is then e.g. 0x0001) or by changing to a different DPT (e.g. 5.005) in the ETS.
Prerequisites for visibility
•
–
Option
Actuator channel
–
Basic-stage heating [actuator]
\
Option
Activated
Heating/cooling changeover
Channel X – Actuator
DPT 1.100
1 bit
C
W T U
This group object is used to receive the change of the operating mode (
heating
/
cooling
) via the bus (ABB i-bus® KNX).
The operating mode is switched in actuator mode exclusively via this group object.
Telegram value:
•
1 = Heating
•
0 = Cooling
Prerequisites for visibility
•
–
Option
Actuator channel
–
Basic-stage heating [actuator]
\
Option
Activated
–
Basic-stage cooling [actuator]
Option
Activated
Request setpoint adjustment (slave)
Channel X – Actuator
DPT 9.002
2 bytes
C R
T
This group object sends a setpoint adjustment on the bus (ABB i-bus® KNX).
The data point type of the group object depends on the setting in the parameter
Data point type, manual setpoint adjustment
Telegram value:
•
-9 … 9 K
Note
This group object must be connected to the corresponding group object of the controller (master) to ensure master/slave operation functionality.
Prerequisites for visibility
•
\ Option
Actuator channel
•
–
Connect analog room control unit to physical device input a
\
Option
Yes
–
Data point type, manual setpoint adjustment
Option
DPT 9.002 (relative temperature value)
Request setpoint adjustment (slave)
Channel X – Actuator
DPT 6.010
1 byte
C R
T
This group object sends a setpoint adjustment on the bus (ABB i-bus® KNX).
The data point type of the group object depends on the setting in the parameter
Data point type, manual setpoint adjustment
Telegram value:
•
-128 … 127 °C
Note
This group object must be connected to the corresponding group object of the controller (master) to ensure master/slave operation functionality.
Prerequisites for visibility
•
\ Option
Actuator channel
•
–
Connect analog room control unit to physical device input a
\
Option
Yes
–
Data point type, manual setpoint adjustment
Option
DPT 6.010 (meter pulses)
Control value Cooling
Channel X – Actuator
DPT 5.001
1 byte
C
W T U
This group object is used to receive the control value Cooling via the bus (ABB i-bus® KNX). This control value is output via the selected output in operating mode
Cooling
.
Telegram value:
•
0 … 100 %
Note
If DPT 5.001 (percentage) is used for the activation, the value displayed for the group object may vary from the actual value due to rounding differences. The actual
value of the group object can be seen by viewing the hexadecimal value (this is then e.g. 0x0001) or by changing to a different DPT (e.g. 5.005) in the ETS.
Prerequisites for visibility
•
–
Option
Actuator channel
–
Basic-stage cooling [actuator]
Option
Activated
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
169