ABB i-bus® KNX
PARAMETERS
7.4.5
Economy cooling increase
This parameter is used to define the value by which the temperature is to be increased in the
Economy
cooling operating mode. The value is specified as a difference from the parameter
More information: →
Explanation of the operating modes, Page 174
Note
The controller ensures that the setpoint temperature is not fallen below when the actual temperature
decreases. The operating mode is not changed.
Option
0 … 4 … 15 °C
Prerequisites for visibility
– Parameter
\
Option
Controller channel
– Parameter
Basic-stage heating [controller]
all options except
Deactivated
– Parameter
Option
Comfort, Standby, Economy, Building Protection
– Parameter
Setpoint specification and adjustment
Option
Relative
• The parameter is in the parameter window
7.4.6
Standby cooling increase
This parameter is used to define the value by which the temperature is to be increased in the
Standby
cooling operating mode. The value is specified as a difference from the parameter
More information: →
Explanation of the operating modes, Page 174
Note
The controller ensures that the setpoint temperature is not fallen below when the actual temperature
decreases. The operating mode is not changed.
Option
0 … 2 … 15 °C
Prerequisites for visibility
– Parameter
\
Option
Controller channel
– Parameter
Basic-stage heating [controller]
all options except
Deactivated
– Parameter
Options
Comfort, Standby, Economy, Building Protection / Comfort,
Standby, Building Protection
– Parameter
Setpoint specification and adjustment
Option
Relative
• The parameter is in the parameter window
7.4.7
Activate basic-stage heating via
This parameter is used to define whether the control value for activating basic-stage heating is output
via an internal output or a group object.
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
57