Specifications and Application 

• 

Specifications and ordering information are in the Infinity S Ordering Guide available at 

abbpowerconversion.com

 

• 

External Surge Protective Device (SPD) is required on all AC inputs. 

• 

Equipment and subassembly ports: 1. are suitable for connection to intra-building or unexposed wiring or 

 

 

 

 

 

         cabling; 

   

 

 

                    2. can be connected to shielded intra-building cabling grounded at both  

 

 

 

 

 

         ends. 

• 

Grounding / Bonding Network – Connect to an Isolated Ground Plane (Isolated Bonding Network) or an 

Integrated Ground Plane (Mesh-Bonding Network or Common Bonding Network). Failure to properly bond 

the power plant to ground may void the warranty in the event of excessive fault or surge current. 

• 

Installation Environment - Install in Network Telecommunication Facilities, OSP, or where NEC applies. 

• 

Battery return may be either Isolated DC return (DC-I) or Common DC return (DC-C). 

 

Reference Documents 

These documents are available at 

abbpowerconversion.com

 

Document Title 

CC848815341  Galaxy Pulsar Plus Product Manual 

CPB-NES 

Infinity S Power System Brochure 

CC848815325 

Infinity NE Install Guide 

Safety Statements 

• 

Do not install this equipment over combustible surfaces.  

• 

Rules and Regulations - Follow all national and local rules and regulations when making field connections.  

• 

Compression Connectors 

   U. S. or Canada installations - use Listed/Certified compression connectors to terminate Listed/            

     Certified field-wire conductors. 

   All installations - apply the appropriate connector to the correct size conductor as specified by the  

     connector manufacturer, using only the connector manufacturer’s recommended or approved tooling        
     for that connector.  

• 

Electrical Connection Securing:  Torque to the values specified on labels or in the product documentation.  

• 

Cable Dress - dress to avoid damage to the conductors and undue stress on the connectors.  

• 

Circuit Breakers and Fuses 

• 

Use only those specified in the equipment ordering guide. 

• 

Size as required by the National Electric Code (NEC) and/or local codes. 

Safety Tested Limits - Refer to the equipment ratings to assure current does not exceed: 

 

Continuous Load (List 1) - 60% of protector rating 

 

Maximum Load (List 2 - typically end of discharge) - 80% of protector rating. 

• 

GMT Style Fuses - Use only fuses provided with safety caps. 

• 

Field-wired Conductors - Follow all National Electric Code (NEC) and local rules and regulations. 

• 

Insulation rating:  90°C minimum; 105°C (minimum) if internal to enclosed equipment cabinets. 

• 

Size AC field-wired conductors with 75°C ampacity (NEC) equal to or greater than their panel board 

circuit breaker rating. 

• 

AC and DC input disconnect/protection - Provide accessible devices to remove input power in an emergency. 

• 

Alarm Signals - Provide external current limiting protection. Rating 60V, 0.5A unless otherwise noted. 

• 

Grounding - Connect the equipment chassis directly to ground. In enclosed equipment cabinets connect to the 

cabinet AC service ground bus. In huts, vaults, and central offices connect to the system bonding network. 

Summary of Contents for Infinity NE-S

Page 1: ...vers 1 Flat 2 Phillips Wire cutters and strippers Read and follow all safety statements and precautions in this guide Controller Pulsar Plus Controller is presented in this guide Refer to Infinity S Power System Brochure for details and accessories NES2448 23 AC1 PS4 DC1E LVBD 23 wide AC input AC1 Molex AC3 IEC 320 C19 AC5H Terminal Block of Power Slots of Distribution Panels 1 or 2 LVBD option QU...

Page 2: ...AC3 AC5 48V Eco Rectifier blue NE050ECO48ATEZ AC 200 277 VAC 48VDC 50A 40A 20A 20A AC 110 VAC 48VDC 22A 40A 20A 20A DC 30 to 150 Vdc 11A max 48VDC 50A 15A 15A 48V Rectifier blue NE075AC48ATEZ NE075AC48ATEZ AC 200 277 VAC 48VDC 75A 50A1 40A 20A 30A AC 110 VAC 48VDC 25A 40A 20A 20A NE050AC48ATEZ AC 200 277 VAC 48VDC 50A 40A 20A 20A AC 110 VAC 48VDC 22A 40A 20A 20A NE050AC48A AC 208 240 VAC 48VDC 50A...

Page 3: ... and secondary load output Lug Landings 1 4 on 5 8 centers Breakers up to 250A TPS fuses to 70A and GMT style fuses to 12A are available A B 26 each for distribution Panel Lug Landings Landings 1 4 20 studs on 5 8 centers Lug tongue width 0 68 max 3 8 16 studs on 1 centers Lug tongue width 0 68 max Torque 65 in lb 7 16 socket 240 in lb 9 16 socket Two multi pole adapters are required for each mult...

Page 4: ...ases and swings outward Slide the unit into the slot until itengages with the back of the shelf Swing the faceplate closed to fully seat the rectifier Verify the faceplate is latched Step 8 Initial Start Up Verify that all AC DC GND and Controller connections are complete and secure Using a multimeter Verify plant reference ground and chassis ground resistance to side ground bar is less than 0 1 O...

Page 5: ...l setting for most networks Controller Alarm Status The display changes colors Green Normal Amber Minor Alarm Red Critical Major Alarm Some alarms may occur during initial installation example thermal probe fail or Major Minor communication fail Clear these alarms Via Controller Display follow the menu path Menu Control Operation Clear Events or Uninstall Equipment Via web pages or EasyView2 Selec...

Page 6: ... Probe under the terminal connector hardware NOT under the connecting lug Max per system Probes 16 ES771 Modules 6 Battery Temperature Measurement Battery Temperature and Voltage Measurement Ordering Codes DescripƟons CC109142980 QS873A Battery Thermal Probe 150026698 QS873B Ambient Probe CC848817024 B 10 controller to thermal probe wireset CC109157434 B 20 controller to thermal probe wireset CC84...

Page 7: ...r 3 G G PMN_C Power Minor_C 13 W G BK R1 Battery On Discharge 4 BR W R1_C Battery On Discharge_C BD_C 14 W W BK R2 Very Low Voltage VLV 5 S BK R2_C Very Low Voltage_C VLV_C 15 W BK W R3 Fuse Alarm Major FAJ 6 BL BL W R3_C Fuse Alarm Major_C FAJ_C 16 R BL R R4 AC Fail ACF 7 O O R R4_C AC Fail_C ACF_C 17 R R R5 Rectifier Fail RFA 8 G G W R5_C Rectifier Fail_C RFA_C 18 R R G R6 Mult Rectifier Fail MR...

Page 8: ...rs to terminate Listed Certified field wire conductors All installations apply the appropriate connector to the correct size conductor as specified by the connector manufacturer using only the connector manufacturer s recommended or approved tooling for that connector Electrical Connection Securing Torque to the values specified on labels or in the product documentation Cable Dress dress to avoid ...

Page 9: ...with ringer modules hazardous voltages will be present on the ringer output connectors Use the following precautions in addition to proper job training and safety procedures Use only properly insulated tools Remove all metallic objects key chains glasses rings watches or other jewelry Follow Lock Out Tag Out LOTO procedures customer specified site specific or general as appropriate Disconnect all ...

Page 10: ...Page 10 2020 ABB All rights reserved Version Date DescripƟon of the change 6 0 04 15 2021 Updated as per template and added new pictures Change History excludes grammar clarifications ...

Page 11: ...hole or in parts is forbidden without prior written consent of ABB Copyright 2020 ABB All rights reserved We reserve the right to make technical changes or modify the contents of this document without prior notice With regard to purchase orders the agreed particulars shall prevail ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this documen...

Reviews: