Alarm and Signal Connections
Standard Controller Alarm Output Defaults
Pin
PCR_C
Power Critical Alarm Return
TB1.1
PCR
Power Critical Alarm
TB2.1
PMJ_C
Power Major/charger Common Alarm Return
TB1.2
PMJ
Power Major/charger Common Alarm
TB2.2
HV_C
High DC Voltage Alarm Return
TB1.3
HV
High DC Voltage Alarm
TB2.3
R1_C
Rectifier Fail Alarm Return
-
R1
TB1.4
R1
Rectifier Fail Alarm
-
R1
TB2.4
R2_C
AC Fail Alarm Return
-
R2
TB1.5
R2
AC Fail Alarm
-
R2
TB2.5
R3_C
Very Low Voltage Alarm Return
-
R3
TB1.6
R3
Very Low Voltage Alarm
-
R3
TB2.6
R4_C
Ground Fault Indicator Return
-
R4
TB1.7
R4
Ground Fault Indicator
-
R4
TB2.7
R5_C
Surge Protection Fail Alarm Return
-
R5
TB1.8
R5
Surge Protection Fail Alarm
-
R5
TB2.8
R6_C
Battery Test Active Return
-
R6
TB1.9
R6
Battery Test Active
-
R6
TB2.9
R7_C
Check Battery Return – R7
TB1.10
R7
Check Battery – R7
TB2.10
Standard Controller Alarm Input Defaults
Pin
Not Used
TB3.1
Not Used
TB3.2
Remote Group Standby
TB4.1
Remote Group Standby Return
TB4.2
Plant Battery Test
TB5.1
Plant Battery Test Return
TB5.2
Air Conditioning Fail
1
TB6.1
Door Open
1
TB6.2
High External Ambient
1
TB6.3
Low External Ambient
1
TB6.4
Common Input Monitor Return
1
TB6.5
Information: Alarm Relay Jumpers and 1
-
Wire Data reference
Jumpers are located on the top of the controller. Remove DC Panel to access, behind the GFI/SPD panel. Alarm
Relay Jumper Factory Defaults are Open on Alarm.