3 Maintenance
3.4.1. Changing the Battery in the Measuring System
97
3HAC030005-001 Revision: -
©
Copyri
ght 200
6 ABB
.
All ri
ghts res
erved.
5. Connect (A) the new
battery to the serial
measurement board.
Connection (X3).
xx0700000520
6. Refit the battery to the
SMB, using a strap.
7. Check the base cover
gasket.
Replace if damaged.
8. Refit the base cover
using the (12pcs) M6
screws.
Described in section
Replacement of base cover gasket on
9. Update the revolution
counters.
Described in section
Updating revolution counters on page
.
Action
Note
A
Continued