3.7.3. SIS system parameters
General
This section details the system parameters that may be set with estimated values. The values
can be defined by the operating organization as knowledge of the robot's working conditions
are accumulated.
Since the counters are to be used for purposes defined by the user, ABB cannot give any
recommendations regarding their definitions.
The figures below shows the options of parameters to be set.
en0200000049
Operation time limit (service level)
The number of operation hours selected as service interval.
E.g. by setting the value "20,000", the SIS will save this as the nominal time for activating
the alarm, not counting the percentage described below.
Operation time warning
A percentage of the "Operation time limit" specified above.
E.g. by setting the value "90", the SIS will alert the operator 18,000 hours after an operation
time "Reset" was made the last time.
Calendar time limit (service level)
The number of calendar years selected as service interval.
E.g. by setting the value "2", the SIS will save this as the nominal time for activating the
alarm, not counting the percentage described below.
Calendar time warning
A percentage of the "Calendar time limit" specified above.
E.g. by setting the value "90", the SIS will alert the operator after 90% of two years, i.e. 657
days after a calendar time "Reset" was made the last time.
Continues on next page