Removing, battery
Use this procedure to remove the SMB battery.
Note
Action
This is done in order to facilitate
updating of the revolution counter.
Move the robot to its calibration position.
1
DANGER
Turn off all:
•
electric power supply
•
hydraulic pressure supply
•
air pressure supply
to the robot, before entering the robot working area.
2
ELECTROSTATIC DISCHARGE (ESD)
The unit is sensitive to ESD. Before handling the
unit please read the safety information in the sec-
tion
The unit is sensitive to ESD on page 35
3
Shown in figure
Remove the
SMB battery cover
by unscrewing the
attachment screws.
CAUTION
Clean cover from metal residues before opening.
Metal residues can cause shortage on the boards
which can result in hazardous failures.
4
Shown in figure
Pull out the battery and disconnect the
battery
cable
.
5
Shown in figure
Remove the
SMB battery.
Battery includes protection circuits. Only replace
with a specified spare part or with an ABB- ap-
proved equivalent.
6
Refitting, battery
Use this procedure to refit the SMB battery.
Note
Action
DANGER
Turn off all:
•
electric power supply
•
hydraulic pressure supply
•
air pressure supply
to the robot, before entering the robot working
area.
1
Continues on next page
194
Product manual - IRB 6650S
3HAC020993-001 Revision: Z
© Copyright 2004-2018 ABB. All rights reserved.
3 Maintenance
3.4.8 Replacing the SMB battery
Continued
Summary of Contents for IRB 6650S Series
Page 1: ...ROBOTICS Product manual IRB 6650S ...
Page 20: ...This page is intentionally left blank ...
Page 50: ...This page is intentionally left blank ...
Page 210: ...This page is intentionally left blank ...
Page 416: ...This page is intentionally left blank ...
Page 422: ...This page is intentionally left blank ...
Page 426: ...This page is intentionally left blank ...
Page 449: ......