The module was saved to
arg
.
Recommended actions
20197, System data from last shutdown cannot
be found
Description
Normally, all system data is saved on shutdown. The file
containing system persistent data cannot be found. The system
has been started using last good system data saved earlier at
arg
.
Consequences
Any changes made in system configuration or RAPID programs
since
arg
will NOT be available after restart. Any such changes
will have to be re-implemented.
Probable causes
The file containing the saved system data may have been
manually moved or deleted.
Recommended actions
Check the location and availability of the saved system data
file. If acceptable, restart using revert to last auto saved to
accept the last good system data. Reinstall the system.
20199, System SoftStop Rejected
Description
The System Input SoftStop is not allowed.
Recommended actions
20270, Access error
Description
Panel Module access error.
Recommended actions
Examine your I/O configuration files.
20280, Symbol conflict
Description
The signal
arg
defined in the IO configuration conflict with
another program symbol with the same name.
Due on that fact the signal will not be mapped to a program
variable.
Recommended actions
Rename the signal in the IO configuration.
20281, IO configuration error
Description
arg arg
with signal name
arg
has wrong signal type. Found
arg
expected
arg
.
Recommended actions
Change your configuration and restart the controller.
20282, Resource and index exist
Description
Resource
arg
.
Index
arg
.
Recommended actions
20283, Text database is full.
Description
Resource
arg
.
Index
arg
.
Recommended actions
20284, Wrong Signal Type For System Input
Description
The System Input
arg
is configured with an I/O-signal of wrong
type.
The I/O-signal
arg
is of type
arg
and this System Input requires
an I/O-signal of type
arg
.
Recommended actions
Change the configuration for the specified System Input.
20285, Wrong Signal Type For System Output
Description
The System Output
arg
is configured with an I/O-signal of wrong
type.
The I/O-signal
arg
is of type
arg
and this System Output requires
an I/O-signal of type
arg
.
Recommended actions
Change the configuration for the specified System Output.
20286, Not Unique I/O-Signal For System Output
Description
Each System Output must have a unique I/O-signal configured.
It is not possible to configure same I/O-signal to several System
Outputs.
System Output:
arg
.
Continues on next page
Operating manual - Troubleshooting IRC5
133
3HAC020738-001 Revision: AA
© Copyright 2005-2018 ABB. All rights reserved.
5 Troubleshooting by event log
5.4 2 xxxx
Continued
Summary of Contents for IRC5 Compact
Page 1: ...ROBOTICS Operating manual Troubleshooting IRC5 ...
Page 10: ...This page is intentionally left blank ...
Page 40: ...This page is intentionally left blank ...
Page 90: ...This page is intentionally left blank ...
Page 586: ...This page is intentionally left blank ...
Page 588: ......
Page 589: ......