Recommended actions
Check all cables connected to the drive unit. Restart the
controller. Replace the drive unit if faulty.
39520, Communication lost with Drive Module
Description
The main computer has lost contact with drive module
arg
.
Consequences
The system goes to status SYS HALT No operation will be
possible until the fault has been corrected.
Probable causes
This may be due to a cable break, badly connected connector
or high levels of interference in the cable.
Recommended actions
Make sure the cable between control module and drive module
is not damaged and that both connectors are correctly
connected. Make sure no extreme levels of electromagnetic
interference are emitted close to the robot cabling.
39521, Drive Module Communication Warning
Description
There are a large number of communication errors being
detected on the Ethernet link to drive module
arg
.
This can be due to external noise sources interfering with the
cable.
Recommended actions
Check that there are no electromagnetic interference sources
running near the cable or the drive or computer modules.
39522, Axis computer not found
Description
The axis computer in drive module
arg
is not connected to the
main computer.
Consequences
The system goes to system failure state. No operation will be
possible until the fault has been corrected.
Probable causes
This may be due to a cable break, badly connected connectors,
or loss of power supply.
Recommended actions
Make sure that the cable between the main computer and the
axis computer is not damaged and that both connectors are
correctly connected. Make sure that the power supply to the
axis computer is working correctly. Restart the controller.
39523, Unused Axis computer connected
Description
Axis computer in the drive module
arg
is connected to the main
computer but not in use.
Probable causes
This can be due to configuration problem.
Recommended actions
Disconnect the unused axis computer or setup the system to
use the axis computer. Restart the controller.
39524, Drive Module Command timeout
Description
Drive module
arg
does not respond to command
arg
. The
system has stopped the program for safety reasons.
Recommended actions
Check that drive module is powered on. Check the cable
between the main computer and axis computer. Restart the
controller.
39525, Drive Module startup error
Description
The system has failed to complete the initialization phase of
drive module
arg
.
Consequences
The system goes to system failure state.
Probable causes
The system has failed to complete the initialization phase of
the drive module.
Recommended actions
Retry by restarting the controller using the main power switch.
Check for other hardware event log messages.
39526, Axis computer not found in Multi Move
system
Description
The axis computer in drive module
arg
is not connected to the
main computer.
Consequences
The system goes to system failure state. No operation will be
possible until the fault has been corrected.
Probable causes
This may be due to a cable break, badly connected connectors,
missing axis computer switch, or loss of power supply.
Continues on next page
210
Operating manual - Troubleshooting IRC5
3HAC020738-001 Revision: AA
© Copyright 2005-2018 ABB. All rights reserved.
5 Troubleshooting by event log
5.5 3 xxxx
Continued
Summary of Contents for IRC5 Compact
Page 1: ...ROBOTICS Operating manual Troubleshooting IRC5 ...
Page 10: ...This page is intentionally left blank ...
Page 40: ...This page is intentionally left blank ...
Page 90: ...This page is intentionally left blank ...
Page 586: ...This page is intentionally left blank ...
Page 588: ......
Page 589: ......