71312, DeviceNet I/O device explicit connection
not enabled
Description
DeviceNet I/O device
arg
does not have the explicit message
connection enabled.
Recommended actions
Change I/O configuration.
71313, Device command order number not unique
Description
The I/O configuration is invalid.
The device command <
arg
> connected to the I/O device <
arg
>
has the same order number <
arg
> as the device command
<
arg
>.
The order number of device commands connected to the same
I/O device must be unique.
This device command has been rejected.
Recommended actions
Modify the I/O configuration so that device commands on the
same I/O device have unique order numbers.
71315, Max number of device commands
exceeded
Description
The I/O configuration is invalid.
The maximum number,
arg
, of device commands in the I/O
system has been exceeded.
Recommended actions
Modify the configuration of the I/O system (by reducing the
number of device commands) so that the maximum limit is not
exceeded.
71317, I/O device reset
Description
The I/O device
arg
on the network
arg
has been reset through
the device command
arg
, to make sure that the device command
values are activated.
This causes the I/O device to loose contact while it is restarted
but it will regain contact.
Probable causes
A device command for reset has been defined for the I/O device
in the configuration of the I/O system.
71320, Max number of I/O access levels exceeded
Description
The I/O configuration is invalid.
The maximum number,
arg
, of I/O access levels in the I/O
system has been exceeded.
Recommended actions
Modify the configuration of the I/O system (by reducing the
number of I/O access levels) so that the maximum limit is not
exceeded.
71321, Invalid I/O access level
Description
The I/O configuration is invalid.
The I/O signal
arg
has a reference to an invalid/undefined I/O
access level
arg
.
All I/O signals must either omit the access level or refer to an
existing access level.
This I/O signal has been rejected.
Recommended actions
Change I/O access level to one that exist or define a new I/O
access level.
71323, Invalid bit values
Description
The I/O configuration for I/O signal
arg
is invalid.
The minimum bit value
arg
must not be less than
arg
.
The maximum bit value
arg
must not exceed
arg
.
The minimum bit value must be less than the maximum bit
value.
This I/O signal has been rejected.
Recommended actions
Check that the I/O signal is configured with the correct encoding
type. Check that the min and max bit values are correct.
71324, Physical limitation values out of range
Description
The I/O configuration for I/O signal
arg
is invalid.
The physical limitation minimum value must be less than the
physical limitation maximum value.
This I/O signal has been rejected.
Recommended actions
Correct the physical limitation values for the I/O signal so that
the minimum value becomes less than the maximum value.
Continues on next page
Operating manual - Troubleshooting IRC5
377
3HAC020738-001 Revision: AA
© Copyright 2005-2018 ABB. All rights reserved.
5 Troubleshooting by event log
5.8 7 xxxx
Continued
Summary of Contents for IRC5 Compact
Page 1: ...ROBOTICS Operating manual Troubleshooting IRC5 ...
Page 10: ...This page is intentionally left blank ...
Page 40: ...This page is intentionally left blank ...
Page 90: ...This page is intentionally left blank ...
Page 586: ...This page is intentionally left blank ...
Page 588: ......
Page 589: ......