Consequences
No communication on the EtherNet/IP is possible. There may
be consequential errors from configuring EtherNet/IP when no
such option has been installed.
Probable causes
An attempt may have been made to add the EtherNet/IP
functionality, without installing the option correctly.
Recommended actions
If the EtherNet/IP option is required: configure a new system
with this option, and install the system. If the EtherNet/IP option
is not required: configure a new system without this option, and
install the system.
71452, Too many EtherNet/IP networks are
configured
Description
Too many EtherNet/IP Industrial Networks are configured. There
is only possibly to have one network for the EtherNet/IP
Scanner/Adapter option.
Recommended actions
Remove one of the EtherNet/IP Industrial Networks from the
I/O configuration. Restart the controller.
71453, Wrong identity for EtherNet/IP adapter
Description
The identity for the adapter
arg
in the I/O configuration is not
correct.
The correct identity is:
Vendor ID
arg
.
Device Type
arg
.
Product Code
arg
.
Consequences
No contact will be established with this adapter.
Recommended actions
Correct the I/O configuration for the adapter with the identity
information above.
71454, The
arg
address is missing
Description
No IP address is specified for the
arg
network.
Consequences
No communication on the
arg
network is possible.
Recommended actions
Specify a valid IP address in the network configuration. Restart
the controller.
71455, EtherNet/IP connection type unknown
Description
The I/O configuration is invalid.
The unit type
arg
has an invalid/unknown connection type
arg
.
The connection type must be one of the following: MULTICAST
POINT2POINT
Consequences
This unit type has been rejected.
Recommended actions
Correct the connection type of the unit type. Restart the
controller.
71457, The EtherNet/IP gateway address is invalid
Description
It is not possible to have the gateway address same as the IP
address.
Or the gateway address cannot be same as the default
destination 0.0.0.0.
Consequences
The default controller gateway address
arg
will be used and
not the specified gateway address
arg
.
Recommended actions
If no physical gateway is used, do not specify any gateway
address in the configuration. Restart the controller.
71458, Could not change the default gateway
address
Description
If no destination address is specified in the Ethernet/IP
configuration, the default controller gateway address will be
changed. The destination address was not given and the
specified gateway address
arg
was not valid and could not be
used.
Consequences
No communication on the EtherNet/IP network is possible.
Recommended actions
Correct the gateway in the EtherNet/IP network configuration.
Restart the controller.
Continues on next page
Operating manual - Troubleshooting IRC5
387
3HAC020738-001 Revision: AA
© Copyright 2005-2018 ABB. All rights reserved.
5 Troubleshooting by event log
5.8 7 xxxx
Continued
Summary of Contents for IRC5 Compact
Page 1: ...ROBOTICS Operating manual Troubleshooting IRC5 ...
Page 10: ...This page is intentionally left blank ...
Page 40: ...This page is intentionally left blank ...
Page 90: ...This page is intentionally left blank ...
Page 586: ...This page is intentionally left blank ...
Page 588: ......
Page 589: ......