71492, PROFINET diagnostic data reported
Description
The I/O device
arg
has reported diagnostic data on slot
arg
.
arg
71493, PROFINET I/O device auto configured
Description
A new I/O device has been found in the PROFINET configuration
file. This I/O device has been auto configured in the controller
with the following parameters:
Device name:
arg
.
Input bytes:
arg
.
Output bytes:
arg
.
Recommended actions
Edit or delete the configuration. Restart the controller to activate
the I/O device configuration.
71494, PROFINET option key missing
Description
The option key needed to run the
arg
network on the controller
was not detected.
Consequences
No communication on
arg
network is possible.
Probable causes
An attempt may have been made to add the PROFINET
functionality, without installing the option correctly.
Recommended actions
Configure a new system with the PROFINET option, and install
that system. If PROFINET is not required, configure a new
system without this option, and install that system.
71495, PROFINET controller option key missing
Description
The option key needed to run the
arg
network as a PROFINET
controller on the controller was not detected. The I/O device
arg
is not defined as an internal PROFINET device.
Consequences
No communication with the I/O device
arg
is possible.
Probable causes
The installed option key for the
arg
network only supports one
internal PROFINET device.
Recommended actions
Configure a new system with the PROFINET controller/device
option or remove the I/O device
arg
from the I/O configuration.
71498, PROFINET network configuration changed
Description
I/O configuration for the network
arg
have been changed by an
external configuration tool or a connecting controller.
The following values have been changed:
Station name:
arg
.
71499, I/O signals in cross connection has
overlapping device map
Description
The I/O configuration of cross connection
arg
is invalid.
The resultant I/O signal
arg
has an overlapping device map with
the inverted actor I/O signal
arg
.
Using I/O signals with overlapping device map in a cross
connection can cause infinity signal setting loops.
Consequences
The cross connection has been rejected, and no functions
depending on it will work.
Recommended actions
Correct the device map or define one of the I/O signals as
simulated.
71500, EtherNet/IP connection failure
Description
Not able to connect to the adapter
arg
.
arg
Consequences
No communication with the adapter is possible.
71501, PROFINET configuration file error
Description
The PROFINET configuration file
arg
was not valid. Internal
error code
arg
.
Consequences
No communication on
arg
network is possible.
Probable causes
The PROFINET configuration file may be corrupt or have been
created with an incompatible file format.
Recommended actions
Generate a new PROFINET configuration file.
Continues on next page
Operating manual - Troubleshooting IRC5
391
3HAC020738-001 Revision: AA
© Copyright 2005-2018 ABB. All rights reserved.
5 Troubleshooting by event log
5.8 7 xxxx
Continued
Summary of Contents for IRC5 Compact
Page 1: ...ROBOTICS Operating manual Troubleshooting IRC5 ...
Page 10: ...This page is intentionally left blank ...
Page 40: ...This page is intentionally left blank ...
Page 90: ...This page is intentionally left blank ...
Page 586: ...This page is intentionally left blank ...
Page 588: ......
Page 589: ......