Action
The calibration summary page for the selected mechanical unit is displayed.
4
Calibration method used at factory for each axis is shown, as well as calibration
method used during last field calibration.
Tap
Calibration Methods
on the right pane.
5
The calibration options are displayed.
Tap
Revolution Counters
.
6
In the
Selection
column select the axes for which revolution counters need to be up-
dated.
7
Tap
Update
.
A dialog box is displayed, warning that the updating operation cannot be undone:
•
Tap
Update
to proceed with updating the revolution counters.
•
Tap
Cancel
to cancel updating the revolution counters.
Tapping
Update
and a confirmation window is displayed.
8
Tap
OK
.
9
The revolution counter for the selected axes is updated.
CAUTION
If a revolution counter is incorrectly updated, it will cause incorrect track positioning,
which in turn may cause damage or injury!
Check the synchronization position very carefully after each update. See
the synchronization position on page 359
.
10
Product manual - IRT 710
343
3HKA00000186299-001 Revision: B
© Copyright 2023 ABB. All rights reserved.
6 Calibration
6.3.1 Updating revolution counters for axis calibration
Continued
Summary of Contents for IRT 710
Page 1: ...ROBOTICS Product manual IRT 710 ...
Page 14: ...This page is intentionally left blank ...
Page 58: ...This page is intentionally left blank ...
Page 84: ...This page is intentionally left blank ...
Page 360: ...This page is intentionally left blank ...
Page 364: ...This page is intentionally left blank ...
Page 378: ...This page is intentionally left blank ...
Page 380: ...This page is intentionally left blank ...
Page 383: ......