background image

 

 

Page 12

 

© 2021 ABB. All rights reserved.

 

 

Version 1.0

 

Step 5 –

  

Connect DC Output 

 

• 

There are 16 DC terminal Outputs and 16 DC Output Returns 

-

 8 per Power Express Converter Module. 

 

• 

Strip the output wire 

1/2”. 

 

• 

Push the screw driver into release hole (#0 Phillips or 

1/8” 

flat screw driver) at a downward angle.

 

• 

Insert wire fully into wire entry.

 

• 

Pull wire to verify insertion. 

 

 

Figure  9:  DC Output Connection

 

Step 6 

-

 Set Controller Jumpers

 

• 

LAN port may be temporarily set to Local mode, but must be set to Network mode for remote monitoring. 

 

• 

Alarm relays may be set to 

Open on Alarm

” 

or 

Close on Alarm

” 

 

Figure  10:  Controller Jumpers

 

Release Hole

 

Local/Network 

Jumper

 

USB Craft Port

 

Alarm relay 

jumpers

 

Wire Entry 

 

24 

-

 8 gauge 

 

-

48V DC Output Terminals

 

DC Output Return Terminals

 

QUICK START GUIDE

 

Summary of Contents for J2007003L301A

Page 1: ...100 120VAC 15A 200 240VAC 7 5A OUTPUT 16 x 42 TO 57VDC 100VA PER CHANNEL Quick Start Guide 8600427867P QUICK START GUIDE This equipment is not suitable for use in locations where children are likely to be present This equipment is intended only for use in a RESTRICTED ACCESS AREA ...

Page 2: ...ire Battery Temp and Voltage monitor 14 Step 10 Install Rectifiers 14 Step 11 Verify Shelf ID Setting 14 Step 12 Initial Converter Modules 14 Step 13 Initial Start Up 14 Step 14 controller per galaxy pulsar edge controller 15 Information Alarm Card LEDs and Alarm 15 Information Converter Module LEDs 15 Information Circuit ON OFF and Load Detection Circuit ON 16 Information Manual Module Operations...

Page 3: ...ry 11 Figure 9 DC Output connection 12 Figure 10 Controller Jumper 12 Figure 11 Controller Installation 13 Figure 12 Alarm Connection 13 Figure 13 Rectifier Installation 14 Figure 14 Shelf ID setting 14 Figure 15 Converter module installation 14 Figure 16 Alarm Card 15 Figure 17 Module LEDs 15 Figure 18 Module LEDs Button 16 Table of Tables Table 1 SPS Shelf Variants 4 Table 2 Shelf LED and Alarm ...

Page 4: ... indications with a controller The AC input and DC output connections are available at the rear side of the panel The Slimline power system shelf with IEC C19 AC input measures 44mm 1 73 x 440 7mm 17 35 x 300 22mm 11 82 H x W x D The Slimline power system shelf with Terminal block AC input measures 44mm 1 73 x 440 7mm 17 35 x 335 02mm 13 19 H x W x D SPS Shelf variants with Part number Description...

Page 5: ...Page 5 2021 ABB All rights reserved Version 1 0 Mounting Dimensions Figure 2 J2007003L301A and J2007003L301AB Dimensions Figure 3 J2007003L301C and J2007003L301CB Dimensions QUICK START GUIDE ...

Page 6: ...Page 6 2021 ABB All rights reserved Version 1 0 Customer Care 1 877 546 3243 Reference Documents Documents Title J2007003 AD SPS POWER EXPRESS SHELF ASSEMBLY DRAWING QUICK START GUIDE ...

Page 7: ...o assure current does not exceed Continuous Load List 1 60 of protector rating Maximum Load List 2 typically end of discharge 80 of protector rating Field wired Conductors Follow all National Electric Code NEC and local rules and regulations Insulation rating 90 C minimum 105 C minimum if internal to enclosed equipment cabinets Size AC field wired conductors with 75 C ampacity NEC equal to or grea...

Page 8: ...h ringer modules hazardous voltages will be present on the ringer output connectors Use the following precautions in addition to proper job training and safety procedures Use only properly insulated tools Remove all metallic objects key chains glasses rings watches or other jewelry Follow Lock Out Tag Out LOTO procedures customer specified site specific or general as appropriate Disconnect all pow...

Page 9: ...Page 9 2021 ABB All rights reserved Version 1 0 Equipment Identification Product Label QUICK START GUIDE ...

Page 10: ...e using three screws on each side four on each side 12 24 provided 3 Torque to 35 in lb 4Nm 5 16 socket 4 Provide 2 inch minimum clearance at back of shelf for converter airflow Step 2 Connect Chassis Ground 1 Lug Landings 10 double hole on 5 8 inch center lugs not provided 2 Minimum 10 AWG wire is recommended 3 Torque to 30 in lb 3 4Nm 5 16 socket Some applications may rely on frame mounting scre...

Page 11: ...t screw driver Connect the 3 pin female connector to the AC input terminal of the shelf Mount the AC cover back over the input and tighten the thumb screw Danger Turn OFF and lock out tag out the AC source before making AC connections Follow all local and national wiring rules Caution Route AC cables to avoid contact with sharp or rough surfaces that may damage insulation and cause a short circuit...

Page 12: ...ward angle Insert wire fully into wire entry Pull wire to verify insertion Figure 9 DC Output Connection Step 6 Set Controller Jumpers LAN port may be temporarily set to Local mode but must be set to Network mode for remote monitoring Alarm relays may be set to Open on Alarm or Close on Alarm Figure 10 Controller Jumpers Release Hole Local Network Jumper USB Craft Port Alarm relay jumpers Wire Ent...

Page 13: ...ovides Data connection for Battery temperature and voltage monitor Alarm J1 and J2 have detachable blocks which can be used to Wire to office alarms and signals Connect alarm cables to the 10 pin Alarm connector Strip the alarm wire 3 16 Insert wire fully into wire entry 28 16 AWG Tighten screw with 1 16 flat screw driver Insert alarm connector into the chassis Figure 11 Controller Installation J5...

Page 14: ...ify Module Type PE 8CKT LMT MODULE 150027362 There are two converter modules to be fixed in the converter shelves provided Open the latch of the converter module Insert module into the respective slot of the Shelf Close the latch of the converter module Step 11 Verify Shelf ID Setting Set Shelf ID to 00 to operate without a system controller Set Shelf ID to 01 through 98 are read by a controller i...

Page 15: ...K Alarm Module LEDs Condition Module OK LED Module Circuit LEDs2 1 8 Priority1 LED Circuit On G G Circuit OFF G OFF Circuit ON Overcurrent 3 Y Y Circuit Fail 1 R R Comm Fault Alarm Card 4 R BLINK Per circuit Condition Module Fail 1 R OFF Input Voltage Out of Range 2 Y BLINK OFF Input Voltage Very Low or Reversed Polarity OFF OFF Table 2 Shelf LED and Alarm Table 3 Module LED Status Circuit LED Fig...

Page 16: ...odule Operations Manually Scan Circuit Loads Press and release the Button no interruption of power to ON circuits Manual Circuit ON OFF 1 Press and hold the Button to enter the manual mode hold until the OK LED turns OFF and back ON 2 seconds 1 Tap the Button repeatedly until the desired Circuit LED blinks Circuit ON LED ON with brief blink OFF Circuit OFF LED OFF with brief blink ON 3 Press and h...

Page 17: ... Change alarm descriptions via LAN port Web pages or Craft port EasyView2 when required Table 4 J1 Alarm Connections Table 5 J2 Alarm Connections Information Fault Detection Circuit ON Output is powered unless over loaded power exceeds 100VA Overloads are retested every 4 sec Circuit OFF Output is unpowered Circuit Load Detection Circuits are scanned for loads upon module power up and upon manual ...

Page 18: ... com External Surge Protective Device SPD is required on all AC inputs Equipment and subassembly ports 1 are suitable for connection to intra building or unexposed wiring or cabling 2 can be connected to shielded intra building cabling grounded at both ends Grounding Bonding Network Connect to an Isolated Ground Plane Isolated Bonding Network or an Integrated Ground Plane Mesh Bonding Network or C...

Page 19: ...Page 19 2021 ABB All rights reserved Version 1 0 Version Date Description of the change 1 0 12 22 2021 Initial Release Change History excludes grammar clarifications QUICK START GUIDE ...

Page 20: ...pt any responsibility whatsoever for potential errors or possible lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB Copyright 2021 ABB All rights reserved ABB 601 Sh...

Reviews: