Page 12
© 2021 ABB. All rights reserved.
Version 1.0
Step 5 –
Connect DC Output
•
There are 16 DC terminal Outputs and 16 DC Output Returns
-
8 per Power Express Converter Module.
•
Strip the output wire
1/2”.
•
Push the screw driver into release hole (#0 Phillips or
1/8”
flat screw driver) at a downward angle.
•
Insert wire fully into wire entry.
•
Pull wire to verify insertion.
Figure 9: DC Output Connection
Step 6
-
Set Controller Jumpers
•
LAN port may be temporarily set to Local mode, but must be set to Network mode for remote monitoring.
•
Alarm relays may be set to
“
Open on Alarm
”
or
“
Close on Alarm
”
Figure 10: Controller Jumpers
Release Hole
Local/Network
Jumper
USB Craft Port
Alarm relay
jumpers
Wire Entry
24
-
8 gauge
-
48V DC Output Terminals
DC Output Return Terminals
QUICK START GUIDE