J DF 3 0 0 |
FI EL D I N D I C ATO R | O I/J D F 3 0 0 - EN R E V. B
21
Idx
Parameter
Description / Range / Selections / Notes
59
FD_FAIL_ALM
Fail Alarm Object
60
FD_OFFSPEC_ALM
Out of Spec Alarm Object
61
FD_MAINT_ALM
Maintenance Alarm Object
62
FD_CHECK_ALM
Function Check Alarm Object
63
FD_FAIL_PRI
Fail error priority
64
FD_OFFSPEC_PRI
Out of Spec error priority
65
FD_MAINT_PRI
Maintenance error priority
66
FD_CHECK_PRI
Function Check error priority
67
FD_SIMULATE
Disabled by default
The simulation can be enabled only if the SW4 of the
electronics is moved to Simulation Enable position
68
FD_RECOMMEN_ACT
Code identifying what should be done to alleviate the anomalous condition. In case of more error conditions
detected, this code refers to the most severe/critical
0 is defined as Not Initialized, 1 is defined as No Action Required, all others defined by manufacturer
69
SPECIAL_RESTART
Bit
11
AR pre-setting
After the selection of one or more blocks of this list is
written to SPECIAL_RESTART, then the operation is really
executed writing the command “Special Restart” in the
RB_RESTART.
All the selected Blocks are configured to a pre-defined
setting allowing their switching to AUTO Mode.
PS: The Function Blocks must have been previously
instantiated into a Function Block Application otherwise
cannot move out from OOS.
Bit
12
IS pre-setting
Bit
14
PID1 pre-setting
Bit
23
PID2 pre-setting
Bit
25
CS pre-setting
Bit
29
MAO-pre-setting
Bit
30
RB pre-setting
70
SPECIAL_OPERATION
0
Do nothing
No Special Operations available in the JDF300
71
MESSAGE
Message
72
DESCRIPTOR
Descriptor
73
INSTALLATION_DATE
Installation date
74
LOCAL_OPERATIONS
0
disabled
Local operation via PUSH BUTTONS are not allowed
1
Enabled (default)
Local operation via PUSH BUTTONS are allowed
75
DEVICE_SER_NUM
Serial Number of the Field indicator as printed on the main Type Plate (on the housing)
and to be used as final part
of the DEV_ID