background image

IB 6.2.11.1-2C 

Page 18 

ABB 

other means for reapplying the lubricants listed. 
 
1. Apply NO-OX-ID special grade A grease from 
Dearborn Chemical Company to all mating surfaces of 
moving current carrying joints.  Do not apply NO-OX-ID 
grease on any main or arcing contact surfaces.  
Primary disconnects should be maintained by 
reapplying NO-OX-ID during maintenance periods.  
NO-OX-ID is available from ABB in one pint cans, part 
number 713222A00. 
 
2. Apply Anderol 757 synthetic grease manufactured by 
HULS AMERICA, INC. to mechanism parts, bearings 
and pins.  Anderol 757 is also to be used on the 
external reduction gearing of the spring charging motor.  
DO NOT APPLY GREASE TO LATCH OR ROLLER 
SURFACES.  Anderol 757 is available from ABB in four 
ounce tubes, part number 712994A00. 
 
3. Anderol synthetic lubricant is also available as a 
spray, Anderol 732.  Anderol 732 is useful as a solvent 
for removing old lubricant, dirt, and debris in the 
mechanism.  It can NOT be used as a substitute for 
Anderol 757.  
 
4. Use only the recommended lubricants.  Use of other 
than approved lubricants can cause breaker 
misoperation at temperature extremes.  
 
Please observe the following additional warnings: 
 
a. DO NOT apply light machine oil, or thin spray 
lubricants to lubricate any mechanism part.  
 
b. DO NOT attempt to relubricate internal components 
of the spring charging motor. It is sealed and should not 
require repacking.  Lubrication should only be applied 
to the external reduction gearing per item 2 above. 
 
c. DO NOT lubricate magnetic latch device or otherwise 
clean or spray with any substance. 
 
 
 
 
 

DIELECTRIC WITHSTAND TESTS ON POWER AND 
CONTROL CIRCUITS 

 
1. Dielectric withstand tests on circuit breakers may be 
made to determine the ability of the insulation to 
withstand overvoltages. 
 
2. A 60-cps alternating sinusoidal voltage (rms) value 
equal to the specific voltage shall be used.  All voltages 
used in the dielectric withstand test shall be measured 
in accordance with ANSI Measurement of Voltage in 

Dielectric Tests, C68.1.  
 
3. Duration Of Test.  The dielectric test voltage shall be 
applied for a period of 60 seconds.  The duration of the 
test may be one second if a voltage 30% greater than 
that specified is applied. 
 
4. Condition Of Circuit Breaker To Be Tested. 

 

Dielectric tests shall be made on a new, completely 
assembled circuit breaker and not on individual parts.  
When a circuit breaker is tested in the field or after 
storage, the test voltage shall be 75% of the value 
listed in ANSI C37.50, 3.5.2 (value shown below). 
 
5. Temperature At Which Tests Are To Be Made.  
Dielectric tests shall be made at any temperature 
between 10 and 55 °C. 
 
6. Magnitudes And Point Of Application Of Test 
Voltage.  The dielectric test shall be applied as follows:  
 
a. With circuit sreaker in open position, apply 2200 
volts (1000 volts plus twice 600 volts on new breakers; 
0.75 x 2200 = 1650V on breakers that have been in 
service): 
 

i.   Between live parts, including both line and load 

terminals, and metal parts that are normally 
grounded.  

 
ii.    Between !ive terminals and load terminals.  

 
b. With circuit breaker in closed position, apply 2200 
volts on new breaker and 1650 volts on breakers that 
have been in service: 
 

i.   Between live parts and metal parts that are 

normally grounded.  

 
ii.    Between terminals of different phases.  

 
c. With circuit breaker in either open or closed position, 
apply 1500 volts (1125 volts on breakers taken out of 
service): 
 
Note: Disconnect solid state trip unit, as a precaution. 
 

i.   Between control circuit and metal parts that are 

normally grounded.  If the circuit breaker control 
circuit includes a motor, the motor 

MUST

 be 

disconnected during the dielectric test on the 
control circuit.  

Summary of Contents for K-Line Plus KP-32

Page 1: ...IB 6 2 11 1 2C Installation Maintenance Instructions Low Voltage Power Circuit Breaker K Line Plus Types KP 32 KPE 32 KP 40 and KPE 40 ABB ...

Page 2: ...CE FOR EO BREAKERS 10 CLOSING SPRING OPERATION 11 INSTALLATION INITIAL TESTING REMOVAL 11 Installation 11 Checking Breaker Operation in TEST 11 Checking Breaker Operation in CONNECTED 11 Manual Closing Operation 12 Circuit Breaker Removal 12 MAINTENANCE AND ADJUSTMENTS 12 Periodic Maintenance Inspection 12 Arc Chutes 12 Insulation Structure 13 MPSC 2000 Trip Device Removal Installation 13 Electric...

Page 3: ...inal carton covering with waterproof paper and sealing to prevent infiltration of dirt Where conditions of high humidity prevail the use of heaters is recommended BASIC HANDLING Once the circuit breaker has been unbolted and removed from its shipping carton it should be turned to the upright position and placed on a flat surface to avoid damage to breaker parts For safety all handling in this posi...

Page 4: ...ip indicator is pushed in the circuit breaker mechanism can then be operated to close the circuit breaker contacts Padlocking Device Figure 1 Item 13 All K Line Plus circuit breakers are equipped with means of padlocking the circuit breaker mechanism in a trip tree position This is accomplished by the use of a locking plate to maintain the manual trip button in a tripping direction when the lockin...

Page 5: ...ional 10 Manual Trip Button 11 Drawout Lever 12 Manual Close Lever 13 Padlock Hasp 14 Motor Disconnect Switch EO only 15 Automatic Trip Indicator 16 Manual Charging Handle Optional 17 Position Indicator Label 18 Spring Charging Motor EO only 19 Racking Cam Rollers 20 Electrical Trip Close Buttons Optional Not Shown Figure 1 Typical Electrically Operated K Line Plus Circuit Breaker 1 19 3 4 5 18 17...

Page 6: ... 4 3 TC 1 51 2 a AS Trip Control Device 5 P18 A5 P4 P20 P8 2 P6 A2 P2 P19 P22 P1 P10 Solid State 3A 1 3 A3 P17 4 Trip A4 2 P5 4A 1 7 P9 P3 80 19 17 15 A14 A18 A16 23 21 A22 A20 14 18 16 20 22 A15 A21 A19 A17 A23 5 6 AS a 10 AS 9 a 12 AS 11 b 14 AS 13 a 16 AS 15 b 53 65 CSCS CSCS 64 63 56 57 NO C C NO B21 32 31 B22 B13 B9 B11 B7 34 32 36 B15 B17 B19 38 40 42 44 19 17 18 a AS 20 21 23 b AS 22 AS a 2...

Page 7: ...5 Not Used supplied with the breaker for pin out assignments 6 The assignments for pins B3 B6 will differ depending on whether the DESP option has been supplied See the MPSC 2000 schematic supplied with the breaker Notes 1 These assignments are provided for reference only and may be changed due to special requirements Some pins or plugs may not be present on all breaker configurations See the brea...

Page 8: ...ical closing functions of the breaker The anti pump feature of the SSCD prevents a second electrical closing until the first closing signal is released For example if the breaker is closed electrically and the signal is maintained the SSCD will not permit the breaker to be closed electrically again after a trip until the electrical close signal is released Shunt Trip The shunt trip is standard on ...

Page 9: ...the tripping energy from the primary current passing through the circuit breaker without the need for any additional power supply An external 9V battery is supplied to permit the user to access the MPSC 2000 s menus The battery is not required for correct operation of the trip device The battery will last only about 1 2 hours of actual use so the switch to this battery should be left in the off po...

Page 10: ...npacked from the factory may have the target displayed as a result of the factory testing performed on the breaker prior to shipping This target will reset when the circuit breaker is closed and sufficient primary current is flowing Continuous monitoring of the microprocessor function is programmed into the MPSC 2000 Watchdog circuits guard against the possibility of microprocessor disfunction due...

Page 11: ...See Figure 1 The circuit breaker must be in the OPEN position the racking crank 8 Figure 1 when inserted in opening is rotated counterclockwise until the racking cam roller 19 is rotated down into a 45 angle and the motor disconnect switch 14 for electrically operated circuit breakers is in the OFF position NOTE Lever 11 must be pushed down to permit the rotation of crank 8 Open compartment door a...

Page 12: ...nd close door MAINTENANCE AND ADJUSTMENTS SAFETY NOTES When it is necessary that the charging springs be charged or the circuit breaker be closed make sure to stay clear of operating parts Breakers shouId be withdrawn to TEST position for checking the breaker operation For further inspection adjustments cleaning or replacement of parts the circuit breaker should be withdrawn from the cell and move...

Page 13: ...dition the breaker will not be able to provide circuit protection NOTE Metallic screws must not be used to retain the trip system harness Should a metallic screw fall into the trip system serious damage can result Electrical Components EO Breakers Only 1 Rack the circuit breaker to the TEST position Make sure the closing springs are charged 2 Operate the local if installed or remote electrical clo...

Page 14: ...mp charging handle until the circuit breaker closing springs are heard to snap into the charged position also check the indicator 6 c Remove screw shift the shutter to the left and insert the spring retainer bracket so that its tips fit into the closing springs and its flanges fit into the holes in the closing spring guides NOTE Shutter cannot be opened unless breaker drawout mechanism is in the D...

Page 15: ...s the primary latch roller from moving to the left and opening the breaker If none of the various trip devices are acting on the tripper bar or the auxiliary latch tripper to open the breaker or to prevent the breaker from closing and the breaker still will not close then the following adjustment should be made a Turn screw 1 Figure 5 down to insure that the secondary trip latch will hold the seco...

Page 16: ...s one equal to the maximum frame continuous current rating of the breaker mounted current sensors and one equal to half the frame rating For example on an 4000A breaker with 4000A sensors the MPSC 2000 rating can be set to 4000A or 2000A When the rating is changed other available settings are scaled accordingly thus the term Range Selection Instantaneous or Short Time Threshold Test 1 Either disab...

Page 17: ...ly from twice to four times the Range Selection and that the trip curve is fixed and does not vary with pickup settings 7 Set test current so that it represents 1 5 times the ST Pickup setting Delays should be as shown in Table 4 Ground Trip Delay Tests Ground Trip Delay tests are performed by injecting current through a single phase of the breaker which appears to be a ground fault to the trip de...

Page 18: ...insulation to withstand overvoltages 2 A 60 cps alternating sinusoidal voltage rms value equal to the specific voltage shall be used All voltages used in the dielectric withstand test shall be measured in accordance with ANSI Measurement of Voltage in Dielectric Tests C68 1 3 Duration Of Test The dielectric test voltage shall be applied for a period of 60 seconds The duration of the test may be on...

Page 19: ...a short circuit ii Motors that have been in service may fail dielectric due to a normal accumulation of debris from the commutator Cleaning the motor will restore dielectric integrity iii Do not perform dielectric testing on the solid state trip system RENEWAL PARTS ABB recommends only those renewal parts be stocked that will be required to insure proper and timely maintenance of the breaker ...

Page 20: ...IB 6 2 11 1 2C Page 20 ABB NOTES ...

Page 21: ...IB 6 2 11 1 2C Page 21 ABB NOTES ...

Page 22: ...IB 6 2 11 1 2C Page 22 ABB ABB Inc P O Box 100524 Florence South Carolina 29501 Phone 843 413 4700 Fax 843 413 4850 ABB ...

Reviews: