background image

IB 6.2.11.1-2C 

Page 3 

ABB 

INTRODUCTION 

 
The KP-32/40 family of circuit breakers are low voltage 
AC power circuit breakers featuring draw-out 
construction and the MPSC-2000 microprocessor-
based trip system with RMS sensing.  These circuit 
breakers can be furnished with either electrically 
operated (EO) or manually operated (MO) 
mechanisms.  On EO models, various control power 
combinations are available, and numerous options are 
available for both mechanism styles. 
 
These instructions apply to the ANSI-rated “KP” series 
(KP-32 and KP-40), and the extended-rated “KPE” 
series (KPE-32 and KPE-40).   
 
An electrically operated, drawout type circuit breaker is 
shown in Figure 1, with a typical schematic diagram 
shown in Figure 2.  
 
These instructions should be read thoroughly before 
handling, installing and/or operating the circuit breaker.  
 
 

RECEIVING AND STORAGE 

 
Immediately upon receipt of the circuit breakers, 
examine the cartons to determine if any damage or loss 
was sustained during transit.  If injury or rough handling 
is evident, file a damage claim at once with the carrier 
and promptly notify the nearest District Office.  The 
Company is not responsible for damage of goods after 
delivery to the carrier.  However, the Company will lend 
assistance if notified of claims. 
 
Unpack the circuit breakers as soon as possible after 
receipt.  If unpacking is delayed, difficulty may be 
experienced in making a claim for damages not evident 
upon receipt.  Use care in unpacking in order to avoid 
damaging any of the circuit breaker parts.  Check the 
contents of each carton against the packing list before 
discarding any packing material.  If any shortage of 
material is discovered, promptly notify the nearest 
District Office.  Information specifying the purchase 
order number, carton number and part numbers of the 
damaged or missing parts should accompany the 
claim. 
 
Circuit breakers should be installed in their permanent 
location as soon as possible (see Basic Handling 
below).  If the breakers are not to be placed in service 
for some time, it is advisable to provide adequate 
means of protection.  This may he done by keeping the 
breaker in its original carton, covering with waterproof 
paper and sealing to prevent infiltration of dirt.  Where 
conditions of high humidity prevail, the use of heaters is 
recommended. 

 
 

BASIC HANDLING 

 
Once the circuit breaker has been unbolted and 
removed from its shipping carton, it should be turned 
to the upright position and placed on a flat surface to 
avoid damage to breaker parts.  For safety, all 
handling in this position should utilize the lifting yoke 
(9) shown in Figure 1. 
 
 

CIRCUIT BREAKER RATING 

 
The circuit breaker continuous current rating (in 
hundreds of amps) is given by the number which 
follows the type designation (e.g., KP-40 = 4000A).  If 
required, the breakers can be fitted with lower ampere 
current sensors and trip systems, which provide 
tripping below the actual continuous current rating of 
the frame size. 
 
Exceeding the continuous current rating of the circuit 
breaker for extended periods may raise the 
temperature of the circuit breaker beyond the limits 
set forth in ANSI C37.13 thus affecting the life of the 
circuit breaker insulating materials.  The MPSC-2000 
trip system has a tolerance band on long time of 
minus zero, plus ten percent (-0, +10%) which will 
allow the circuit breaker to carry its rated continuous 
current but will provide tripping above that value. 
Additionally, root mean square (RMS) current 
calculation on the long time trip element provides 
tripping based on the true heating value of the current 
passing through the circuit breaker. 
 
 

ESCUTCHEON OPERATlNG FEATURES 

 
Manually and electrically operated circuit breakers are 
provided with an extended escutcheon face plate.  
This escutcheon provides a central area for the 
controls which are mounted directly on the circuit 
breaker.  Figure 1 shows the controls and other 
features provided on a typical electrically operated 
circuit breaker.  The controls for manually operated 
circuit breakers are the same, except that the manual 
charging handle (16) is standard and the charge 
motor and its cut-off switch are not provided. 
 
A self-aligning plate, immediately behind the 
escutcheon face plate, is used to exclude dust from 
the circuit breaker compartment.  The escutcheon 
face will protrude through the front door of the 
compartment when the circuit breaker is in the “TEST” 
and "DISCONNECTED" positions.  In these positions, 
the dustplate still functions to exclude dust. 

Summary of Contents for K-Line Plus KP-32

Page 1: ...IB 6 2 11 1 2C Installation Maintenance Instructions Low Voltage Power Circuit Breaker K Line Plus Types KP 32 KPE 32 KP 40 and KPE 40 ABB ...

Page 2: ...CE FOR EO BREAKERS 10 CLOSING SPRING OPERATION 11 INSTALLATION INITIAL TESTING REMOVAL 11 Installation 11 Checking Breaker Operation in TEST 11 Checking Breaker Operation in CONNECTED 11 Manual Closing Operation 12 Circuit Breaker Removal 12 MAINTENANCE AND ADJUSTMENTS 12 Periodic Maintenance Inspection 12 Arc Chutes 12 Insulation Structure 13 MPSC 2000 Trip Device Removal Installation 13 Electric...

Page 3: ...inal carton covering with waterproof paper and sealing to prevent infiltration of dirt Where conditions of high humidity prevail the use of heaters is recommended BASIC HANDLING Once the circuit breaker has been unbolted and removed from its shipping carton it should be turned to the upright position and placed on a flat surface to avoid damage to breaker parts For safety all handling in this posi...

Page 4: ...ip indicator is pushed in the circuit breaker mechanism can then be operated to close the circuit breaker contacts Padlocking Device Figure 1 Item 13 All K Line Plus circuit breakers are equipped with means of padlocking the circuit breaker mechanism in a trip tree position This is accomplished by the use of a locking plate to maintain the manual trip button in a tripping direction when the lockin...

Page 5: ...ional 10 Manual Trip Button 11 Drawout Lever 12 Manual Close Lever 13 Padlock Hasp 14 Motor Disconnect Switch EO only 15 Automatic Trip Indicator 16 Manual Charging Handle Optional 17 Position Indicator Label 18 Spring Charging Motor EO only 19 Racking Cam Rollers 20 Electrical Trip Close Buttons Optional Not Shown Figure 1 Typical Electrically Operated K Line Plus Circuit Breaker 1 19 3 4 5 18 17...

Page 6: ... 4 3 TC 1 51 2 a AS Trip Control Device 5 P18 A5 P4 P20 P8 2 P6 A2 P2 P19 P22 P1 P10 Solid State 3A 1 3 A3 P17 4 Trip A4 2 P5 4A 1 7 P9 P3 80 19 17 15 A14 A18 A16 23 21 A22 A20 14 18 16 20 22 A15 A21 A19 A17 A23 5 6 AS a 10 AS 9 a 12 AS 11 b 14 AS 13 a 16 AS 15 b 53 65 CSCS CSCS 64 63 56 57 NO C C NO B21 32 31 B22 B13 B9 B11 B7 34 32 36 B15 B17 B19 38 40 42 44 19 17 18 a AS 20 21 23 b AS 22 AS a 2...

Page 7: ...5 Not Used supplied with the breaker for pin out assignments 6 The assignments for pins B3 B6 will differ depending on whether the DESP option has been supplied See the MPSC 2000 schematic supplied with the breaker Notes 1 These assignments are provided for reference only and may be changed due to special requirements Some pins or plugs may not be present on all breaker configurations See the brea...

Page 8: ...ical closing functions of the breaker The anti pump feature of the SSCD prevents a second electrical closing until the first closing signal is released For example if the breaker is closed electrically and the signal is maintained the SSCD will not permit the breaker to be closed electrically again after a trip until the electrical close signal is released Shunt Trip The shunt trip is standard on ...

Page 9: ...the tripping energy from the primary current passing through the circuit breaker without the need for any additional power supply An external 9V battery is supplied to permit the user to access the MPSC 2000 s menus The battery is not required for correct operation of the trip device The battery will last only about 1 2 hours of actual use so the switch to this battery should be left in the off po...

Page 10: ...npacked from the factory may have the target displayed as a result of the factory testing performed on the breaker prior to shipping This target will reset when the circuit breaker is closed and sufficient primary current is flowing Continuous monitoring of the microprocessor function is programmed into the MPSC 2000 Watchdog circuits guard against the possibility of microprocessor disfunction due...

Page 11: ...See Figure 1 The circuit breaker must be in the OPEN position the racking crank 8 Figure 1 when inserted in opening is rotated counterclockwise until the racking cam roller 19 is rotated down into a 45 angle and the motor disconnect switch 14 for electrically operated circuit breakers is in the OFF position NOTE Lever 11 must be pushed down to permit the rotation of crank 8 Open compartment door a...

Page 12: ...nd close door MAINTENANCE AND ADJUSTMENTS SAFETY NOTES When it is necessary that the charging springs be charged or the circuit breaker be closed make sure to stay clear of operating parts Breakers shouId be withdrawn to TEST position for checking the breaker operation For further inspection adjustments cleaning or replacement of parts the circuit breaker should be withdrawn from the cell and move...

Page 13: ...dition the breaker will not be able to provide circuit protection NOTE Metallic screws must not be used to retain the trip system harness Should a metallic screw fall into the trip system serious damage can result Electrical Components EO Breakers Only 1 Rack the circuit breaker to the TEST position Make sure the closing springs are charged 2 Operate the local if installed or remote electrical clo...

Page 14: ...mp charging handle until the circuit breaker closing springs are heard to snap into the charged position also check the indicator 6 c Remove screw shift the shutter to the left and insert the spring retainer bracket so that its tips fit into the closing springs and its flanges fit into the holes in the closing spring guides NOTE Shutter cannot be opened unless breaker drawout mechanism is in the D...

Page 15: ...s the primary latch roller from moving to the left and opening the breaker If none of the various trip devices are acting on the tripper bar or the auxiliary latch tripper to open the breaker or to prevent the breaker from closing and the breaker still will not close then the following adjustment should be made a Turn screw 1 Figure 5 down to insure that the secondary trip latch will hold the seco...

Page 16: ...s one equal to the maximum frame continuous current rating of the breaker mounted current sensors and one equal to half the frame rating For example on an 4000A breaker with 4000A sensors the MPSC 2000 rating can be set to 4000A or 2000A When the rating is changed other available settings are scaled accordingly thus the term Range Selection Instantaneous or Short Time Threshold Test 1 Either disab...

Page 17: ...ly from twice to four times the Range Selection and that the trip curve is fixed and does not vary with pickup settings 7 Set test current so that it represents 1 5 times the ST Pickup setting Delays should be as shown in Table 4 Ground Trip Delay Tests Ground Trip Delay tests are performed by injecting current through a single phase of the breaker which appears to be a ground fault to the trip de...

Page 18: ...insulation to withstand overvoltages 2 A 60 cps alternating sinusoidal voltage rms value equal to the specific voltage shall be used All voltages used in the dielectric withstand test shall be measured in accordance with ANSI Measurement of Voltage in Dielectric Tests C68 1 3 Duration Of Test The dielectric test voltage shall be applied for a period of 60 seconds The duration of the test may be on...

Page 19: ...a short circuit ii Motors that have been in service may fail dielectric due to a normal accumulation of debris from the commutator Cleaning the motor will restore dielectric integrity iii Do not perform dielectric testing on the solid state trip system RENEWAL PARTS ABB recommends only those renewal parts be stocked that will be required to insure proper and timely maintenance of the breaker ...

Page 20: ...IB 6 2 11 1 2C Page 20 ABB NOTES ...

Page 21: ...IB 6 2 11 1 2C Page 21 ABB NOTES ...

Page 22: ...IB 6 2 11 1 2C Page 22 ABB ABB Inc P O Box 100524 Florence South Carolina 29501 Phone 843 413 4700 Fax 843 413 4850 ABB ...

Reviews: