background image

Effective: April 1981

NEW INFORMATION

ABE Power T&D Company Inc.

Relay Division
Coral Springs, FL 33065

Instruction Leaflet

I.L. 41-498.5

Type KD Compensator

Distance Relays Calibration

and Maintenance Procedures

These instructions are intended to supplement

Instruction Leaflets 41-491, 41-498.11, 41-491.4,

41-498.12 and 41-490, covering the KD-1, 4, 41,
5, 10, and 11 line of compensator distance relays,
respectively. These instructions expand on the in-
formation given in these I.L.'s  and suggest what
elements should be included in a calibration and
maintenance program.

calibration and maintenance program

should involve two steps: 1) a receiving accept-
ance check and 2) a routine (periodic) mainten-
ance program. These two steps are outlined below:

RECEIVING ACCEPTANCE

Received relays should be subjected to the

checks outlined in the applicable I.L. These checks
will insure that there is no shipping damage and
that the relay has been received in the same cali-
brated condition as it left the factory. They will
insure that set-up procedures such as removing

contact blocking has been accomplished. A re-
ceiving acceptance check should include the

following steps:

1. Perform all of the mechanical and electrical

tests listed in the receiving acceptance section
of the applicable I.L., include the maximum
torque angle test, even if it is not called for
in some I.L.‘s.

2. 

Follow the 

appropriate test procedures outlined in

I.L.‘s covering the K-DAR FIELD TEST UNIT.
It is suggested that all dial test readings in each test
be recorded for future reference. This information

3.

will be very helpful in recognizing possible drift of
electrical characteristics.

If the settings to be applied to the relay when it is
installed are known, the relay should be set to

these settings and checked with the field test units
as noted in step 2 above. A record 

for future refer-

ence should be taken. 

The relay test values using

the KDAR test unit should check to be within 2 7
percent of the relay settings.

ROUTINE MAINTENANCE

The relay should be checked periodically at

time intervals dictated by previous experience
and practices. Westinghouse recommends that
the time interval between checks be a maximum
of two years. Routine maintenance should include
at

1.

2.

3.

leas; the following steps:

Repeat step 2 or 3 under Receiving Acceptance

and record test results.

Compare test results with previous results. If
any test values deviate from previous checks
by more than &5 percent, recheck relay per-
formance in line with the receiving acceptance
checks outlined above step 1.

Retain records of test results on each particular
relay. During each routine maintenance, the

records should be analyzed to determine if
there is any evidence of drift; i.e., continued
change in characteristic in the same direction.

Evidence of drift should be traced to the parti-

cular element involved, usually a capacitor or

resistor and this element replaced.

All possible contingencies which may arise during installation, operation or maintenance, and all details

and variations of this equipment do not purport to be covered by these instructions. ff further information
is desired by purchaser regarding this particular installation, operation or maintenance of this equipment,
the local ABB Power T&D Company Inc. representative should be contacted.

 in U.S.A

Summary of Contents for KD-1

Page 1: ...rmation 3 will be very helpful in recognizing possible drift of electrical characteristics If the settings to be applied to the relay when it is installed are known the relay should be set to these settings and checked with the field test units as noted in step 2 above A record for future refer ence should be taken The relay test values using the KDAR test unit should check to be within 2 7 percen...

Page 2: ...ention should be paid to the fact that voltage and current settings will change as the angle is varied To avoid inaccuracies due to this effect check the voltage and current settings when contact operation indicates that maximum torque angle check point has been reached 2 Failure or miscalibration of components not connected with angle adjustment to distin guish between the two sources of error it...

Page 3: ...ome short reach KD 4 If contacts of the 3 phase unit close then the C3C capacitor is under suspicion but im properly adjusted R3A can be suspected as well Step 2 Remove the connections made in Step 1 Apply approximately 120 volts i e 100 130 volts to terminals 8 and 9 Vg9 Measure the voltage across the C3C capacitor with a high impedance voltmeter 5000 OHMS volt For 75 20 OHM reach KD 4 relays the...

Page 4: ...e C3C capacitor If C3C has been found bad shorted or leaky repeat P3A or R3A adjustment above Suggested Procedure for Replacement of CzC C A Capacitors After the capacitors have been replaced a b Open relay switch 9 phase C potential short terminals 7 9 on relay side and apply approximately 120 volts to terminals 7 and 8 c 4 e adjust RCA resistor for KD 4 41 relays and XIAC for KD 10 11 relays so ...

Reviews: