background image

c) for .2-4.35

 OHM 

relays without sub “A”

in style number

for a cold relay, decreases R3A setting

7% of total R3A  + R31z  resistance.

for a hot relay, decrease R3A setting

4% of total R3A + R~F

 reSiStanCe.

NOTE: R3A range of adjustment may occasion-

ally be insufficient. If so, set R~F for
maximum resistance, or replace R~F
resistor with higher value.

d) For KD-10 follow instruction leaflet to ad-

jUSt  R~A OI- P3A.

F)

G.

Suggested procedure for C3C for KD-1, KD-41,
KD-11 relays.

4

b)

No voltage test is required across the C3C

capacitor.

If C3C has been found bad (shorted or

leaky) repeat P3A or R3A adjustment
above.

Suggested Procedure for Replacement of

CzC, C~A Capacitors

After the capacitors have been replaced:

a>

b)

Open relay switch 9 (phase C potential).

short terminals 7 & 9 on relay side and apply

approximately 120 volts to terminals 7 and
8.

c)

4
e)

adjust RCA resistor for KD-4-41 relays
and XIAC  for KD-10-11 relays so contact

just floats - favoring contact opening
direction.

if desired, repeat 2.5 volts calibration point.

for KD & KD-1 relays, follow procedure

for RMA & RMC calibration.

ABB 

Network Partner

ABB Power T&D Company Inc.
4300 Coral Ridge Drive
Coral Springs Florida 33065

(954) 752-6700

FAX: (954)  3455329

Printed 

in 

USA

Summary of Contents for KD-1

Page 1: ...rmation 3 will be very helpful in recognizing possible drift of electrical characteristics If the settings to be applied to the relay when it is installed are known the relay should be set to these settings and checked with the field test units as noted in step 2 above A record for future refer ence should be taken The relay test values using the KDAR test unit should check to be within 2 7 percen...

Page 2: ...ention should be paid to the fact that voltage and current settings will change as the angle is varied To avoid inaccuracies due to this effect check the voltage and current settings when contact operation indicates that maximum torque angle check point has been reached 2 Failure or miscalibration of components not connected with angle adjustment to distin guish between the two sources of error it...

Page 3: ...ome short reach KD 4 If contacts of the 3 phase unit close then the C3C capacitor is under suspicion but im properly adjusted R3A can be suspected as well Step 2 Remove the connections made in Step 1 Apply approximately 120 volts i e 100 130 volts to terminals 8 and 9 Vg9 Measure the voltage across the C3C capacitor with a high impedance voltmeter 5000 OHMS volt For 75 20 OHM reach KD 4 relays the...

Page 4: ...e C3C capacitor If C3C has been found bad shorted or leaky repeat P3A or R3A adjustment above Suggested Procedure for Replacement of CzC C A Capacitors After the capacitors have been replaced a b Open relay switch 9 phase C potential short terminals 7 9 on relay side and apply approximately 120 volts to terminals 7 and 8 c 4 e adjust RCA resistor for KD 4 41 relays and XIAC for KD 10 11 relays so ...

Reviews: