I.L. 41-490H
13
TABLE I
RELAY SETTINGS FOR KD-10 & KD-11 RELAYS (.2 - 4.5 OHMS)
S = 1
S = 2
S = 3
LEAD CONNECTION
∆
T
.230
.307
.383
.537
.690
.920
1.23
.69
.920
1.23
.92
1.23
+M
-M
“L”
Lead
“T”
Lead
.195
.260
.325
.455
.585
.780
1.042
-
1.56
2.08
-
3.13
+.18
-
.06
0
“L
” O
VER “R”
.200
.267
.333
.467
.600
.800
1.070
-
1.60
2.14
-
3.21
+.15
-
.06
.03
.205
.274
.342
.479
.616
.821
1.098
-
1.64
2.20
-
3.29
+12
-
.09
0
.211
.282
.351
.493
.633
.844
1.128
-
1.69
2.26
-
3.39
+.09
-
.09
.03
.217
.290
.361
.507
.651
.868
1.160
-
1.74
2.32
-
3.48
+.06
-
.06
.09
.223
.298
.372
.521
.670
.893
1.194
-
1.79
2.39
-
3.58
+.03
-
.03
0
.230
.307
.383
.537
.690
.920
1.230
-
1.84
2.46
-
3.69
0
0
0
0
.237
.316
.395
.554
.711
.948
1.268
-
1.90
2.54
-
3.80
-
-.03
0
.03
“R” O
VER “L
”
.245
-
.407
.571
.734
.979
1.308
-
1.96
2.62
-
3.93
-
-.06
.09
.06
.253
-
.421
-
.758
1.011
1.352
1.52
2.02
2.70
3.03
4.05
-
-.09
.03
.09
-
-
.435
-
-
-
1.398
-
2.80
-
4.19
-
-.12
0
.09
-
-
.451
-
-
-
1.447
-
2.89
-
4.34
-
-.15
.03
.06
-
-
-
-
-
-
1.50
-
3.00
-
4.5
-
-.18
0
.06
∆
The tap plate values refer to standard maximum torque angle adjustment which is 75
°
for phase-to-phase unit
and 60
°
for three phase unit.