2TLC172250M0201, rev. D
7
www.abb.com/jokabsafety
2013-08-12
3
Connections
Electrical connections
– Knox 2A
Locking
The internal motor will lock Knox when supplied with 24 VDC, with pin-3 as the positive pole (+) and pin-4 as the
negative pole (-).
The locking signals must be applied for at least 2 seconds or until the dynamic output signal from the Eden sensor
is active. There is no maximum time limit; the locking signals may be applied continuously during the time Knox is
locked.
Unlocking
The internal motor will unlock Knox when supplied with 24 VDC, with pin-3 as the negative pole (-) and pin-4 as the
positive pole (+).
The unlocking signals must be applied for at least 2 seconds. There is no maximum time limit; the unlocking signals
may be applied continuously during the time Knox is unlocked.
NB: Knox 2A will retain its locked/unlocked state when power is cut off.
Warning
! All information output signals are non-failsafe and must therefore
never
be used to control a safety
application. To control a safety application the safe dynamic signals from Eden must be used to determine if a door
is locked or not.
Warning!
The system must be connected using a fuse of max 6A.
ADAM
EDEN
Knox 2A
+ 24 V
1
7
6
5
3
4
8
2
Reset
Sensor
Motor
M12 8-pole male seen
from cable side
M12 8-pole female
seen from cable side
8-pole M12-connector:
1 ) White: Dynamic input signal
2 ) Brown: +24 VDC
3 ) Green: Lock
4 ) Yellow: Lock inverse
5 ) Grey: Information Locked
6 ) Pink:
Dynamic output signal
7 ) Blue:
0 VDC
8 ) Red:
Information Reset
Caution!
All cable colours according to ABB Jokab Safety standard cable.
Summary of Contents for Knox
Page 12: ...2TLC172250M0201 rev D 12 www abb com jokabsafety 2013 08 12 Assembly conventional door ...
Page 13: ...2TLC172250M0201 rev D 13 www abb com jokabsafety 2013 08 12 ...
Page 16: ...2TLC172250M0201 rev D 16 www abb com jokabsafety 2013 08 12 Assembly sliding door ...
Page 17: ...2TLC172250M0201 rev D 17 www abb com jokabsafety 2013 08 12 ...