Clean and Grease Breaker
Before installing or operating a breaker, refer to the Emax 2 Breaker installation manual
1SDH001330R0002 for pre-operation inspecting and testing.
Check thoroughly for any damaged or loose parts and for any dirt or foreign matter
which may be on the breaker.
Clean those areas if necessary with a clean, lint-free rag and isopropyl alcohol or acetone.
Be sure to apply a thin film of Mobilgrease #28 to the primary disconnect fingers for
better electrical connections on the breaker, and lower racking force.