24
User Guide
| OI-LLT100-EN Rev. D
LLT100
Laser lever transmitter
7.4 Configuring the filling rate
NOTICE
The fill rate must be set to the process maximum filling
rate to avoid overflows. The instrument sensor smooths
out any change in level that is faster than the entered
filling rate.
The filling rate corresponds to the maximum speed at which a
vessel fills up. Its value is used to limit the maximum possible
rate of change of the level measurement reading during filling.
This feature is used in processes where heavy dust or vapor
can severely decrease the visibility of the level surface or
in which the laser beam can be temporarily obstructed (by
agitators, filling material, etc.)
WARNING
Because of the No Measurement Period feature, there
is a risk of overflow, should the actual filling rate exceed
the configured rate. In the case of hazardous products
(chemicals, etc.), this could constitute a risk to health/
life.
7.4.1 Enabling the filling rate feature
To do so:
1. From the
Device Setup
menu, select
Filtering > Filling
Rate > Enable
.
2. From the
Enable
menu, select whether or not you want to
enable the filter and press
OK
.
7.4.2 Setting the filling rate
To do so:
1. From the
Device Setup
menu, select
Filtering > Filling
Rate > Rate
.
2. From the
Rate
menu, edit the filling rate as necessary (see
also section 7.1) and press
OK
.
7.5 Configuring the draining rate
The draining rate corresponds to the maximum speed at
which a vessel drains. Its value is used to limit the maximum
possible rate of change of the level measurement reading
during drainage.
This feature is used in clear liquid processes where the bottom
of the tank is visible through the surface and in liquid processes
held in highly reflective stainless steel vessels.
NOTICE
This rate must be set to the process maximum draining
rate to avoid equipment (e.g., pumps) running on empty.
The instrument sensor smooths out any change in level
that is faster than the entered draining rate.
7.5.1 Enabling the draining rate feature
To do so:
1. From the
Device Setup
menu, select
Filtering > Draining
Rate > Enable
.
2. From the
Enable
menu, select whether or not you want to
enable the filter and press
OK
.
7.5.2 Setting the draining rate
To do so:
1. From the
Device Setup
menu, select
Filtering > Draining
Rate > Rate
.
2. From the
Rate
menu, edit the draining rate as necessary
(see also section 7.1) and press
OK.
7.6 Enabling damping
Processes can induce noise in level measurements.
The instrument damping filter is designed to smooth out
measurement noise in applications with slow dynamics
(e.g. liquid with slow waves).
The value entered corresponds to the damping time constant
(ranging from 1 s to 3600 s) applied to the measurement
returned by the median filter.
To set a damping time:
1. From the
Device Setup
menu, select
Filtering > Damping >
Damping Time
.
2. In the
Damping Time
menu, edit the duration and press
OK
.
Summary of Contents for LLT100
Page 8: ...This page intentionally left blank ...
Page 10: ...This page intentionally left blank ...
Page 18: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 26: ...This page intentionally left blank ...
Page 44: ...This page intentionally left blank ...
Page 50: ...This page intentionally left blank ...
Page 66: ...This page intentionally left blank ...
Page 67: ......