33
LMT S E R I E S |
M AG N E TOS T R I C T I V E L E V EL T R A N SM I T T ER | O I/L M T 10 0/ 2 0 0 - EN R E V. B
Menu: Easy Setup (continued)
Menu/Parameter
Value Range
Description
Easy Setup
Language
English, Chinese, Portuguese, German, Spanish, French,
Italian
Menu language options
Set PV
Level, Interface, Distance/Ullage, Volume Level, Volume
Interface, Flow
Select device variable where applicable which will be
assigned to the 4-20 mA output and HART primary
variable
PV Unit
• Unit length
- mm, cm, m, in, ft
• Unit volume
- Liters, Cubic meters, cubic inches, cubic feet, cubic
yards, gallons, Imperial gallons, bushels, barrels,
liquid barrels
• Unit flow
- Liters/second, liters/minute, liters/hour, gallons/
second, gallons/minute, gallons/hour, gallons/day,
imperial gallons/ second, imperial gallons/minute,
imperial gallons/hour, imperial gallons/day, barrels/
second, bar rels/minutes, barrels/hour, bar rels/day,
cubic meters/second, cubic meters/minute, cubic
me ters/hour, cubic meters/day, cubic feet/second,
cubic feet/ minute, cubic feet/hour, cubic feet/day
Defines unit of measure for primary variable
PV LRV
Non linearized
Minus 10% to half of probe length
Linearized
-999999999 to 999999999
Sets 4 mA output point which is also the lower range
value of the measuring span
PV URV
Non-linearized
Half to 20% beyond probe length
Linearized
-999999999 to 999999999
Sets 20 mA output point which is also the upper range
value for the measuring span
PV Damping Time
0.1 - 60 seconds
Allows signal smoothing of the 4-20 mA signal.
Display 1 Line 1 View
Level, Interface, Distance/Ullage
Select variable to be viewed on display
Tag
alphanumeric
User defined. 32 characters available.