35
LMT S E R I E S |
M AG N E TOS T R I C T I V E L E V EL T R A N SM I T T ER | O I/L M T 10 0/ 2 0 0 - EN R E V. B
Menu: Device Setup (continued)
Menu/Parameter
Value Range
Description
Device Setup/Write Protect
Software WP
On, Off
Sets ability of user to edit parameters through software
Hardware WP
Unlocked, Locked
Sets ability of user to edit parameters through
mechanical switch on the top of the trasmitter housing
Device Setup/PV Setup
PV Unit
• Unit length
- mm, cm, m, in, ft
• Unit volume
- Liters, Cubic meters, cubic inches, cubic feet, cubic
yards, gallons, Imperial gallons, bushels, barrels,
liquid barrels
• Unit flow
- Liters/second, liters/minute, liters/ hour, gallons/
second, gallons/minute, gallons/hour, gallons/day,
imperial gallons/ second, imperial gallons/minute,
imperial gallons/ hour, imperial gallons/day,
barrels/ second, barrels/minutes, barrels/ hour,
barrels/day, cubic meters/second, cubic meters/
minute, cubic meters/hour, cubic meters/day, cubic
feet/second, cubic feet/minute, cubic feet/hour,
cubic feet/day
Defines unit of measure for primary variable
PV LRV
• Non linearized
- Minus 20% to 120% of probe length
• Linearized
-999999999 to 999999999
Sets 4 mA output point which is also the lower range
value of the measuring span
PV URV
• Non linearized
- Minus 20% to 120% of probe length
• Linearized
-999999999 to 999999999
Sets 20 mA output point which is also the upper range
value for the measuring span
PV Damping Time
0.1 – 60 seconds
Allows signal smoothing of the 4-20 mA signal.
Device Setup/Device
Variables/Level
Level Units
mm, cm, m, in, ft
Sets units for level output type
Lower Range
• Non linearized
- Minus 20% to 120% of probe length
• Linearized
-999999999 to 999999999
Upper Range
• Non linearized
- Minus 20% to 120% of probe length
• Linearized
-999999999 to 999999999
PV Offset
+/- 50% of probe length
Device Setup/Device
Variables/Interface
Lower Range
• Non linearized
- Minus 20% to 120% of probe length
• Linearized
-999999999 to 999999999
Damping Time
0.1-60 seconds
Upper Range
• Non linearized
- Minus 20% to 120% of probe length
• Linearized
-999999999 to 999999999
Interface Offset
+/- 50% of probe length
Device Setup/Device
Variables/Temperature
C, F
select temperature unit of measure
Lower Range
–200°C to 300°C
Upper Range
–200°C to 300°C
Temperature Offset
–200°C to 300°C
Lower Temp Limit
–200°C to 300°C
Upper Temp Limit
–200°C to 300°C