LMT S E R I E S |
M AG N E TOS T R I C T I V E L E V EL T R A N SM I T T ER | O I/L M T 10 0/ 2 0 0 - EN R E V. B
39
For example use the tank in 8 6 2 1-2, where the Diameter is
1000 mm, Length is 2500 mm, Input Unit is mm, Output type is
Volume, Output unit is liters
Point #
00
01
02
03
04
20
Input Value
<In> (mm)
0
100
200
800
900
1000
Output
Value
<Out> (lit)
0
102.19
279.56
1683.94 1861.31
1963.5
Using linearization tables
STEP 1:
Log in as an “Advanced user by pressing
STEP 2:
Press
to navigate to Device Setup menu
Press
to Select/Enter the Device Setup menu
STEP 3:
Press
to navigate to Linearization submenu
Press
to Select/Enter the Linearization menu
IMPORTANT NOTE
All parameters in the following section are edited the same
unless otherwise stated***
Configuring Setup
STEP 1:
Press
or
to highlight setup
Press
to Select/enter into the Linearization setup menu
STEP 2:
Press
to Select/enter into the Table State menu
STEP 3:
Press
to edit the Table State
STEP 4:
Press
or
to highlight an action
Press
to apply the highlighted action